Calculate Size of Diesel Generator for various types of Load
June 21, 2024 Leave a comment
Calculate Size of Diesel Generator set for following types of various equipment’s
D.G Set Detail:
- G Set Phase-Phase Voltage=415V, Phase-Neutral Voltage=230V, Future Load expansion=10%, D.G overload capacity =130%.
Connected Load:
- Fire Fighting Pump: 1No,3 Phase, 90KW, starting P.F is 0.7 & running P.F is 0.8, Soft Starter, Continuous use.
- HVAC Load: 1No, 3 Phase, 20KW, starting P.F is 0.7 & running P.F is 0.8, Intermediate use.
- UPS Load: 1No, 3 Phase, 7KW, starting P.F is 0.7 & running P.F is 0.8, Continuous use.
- Lighting Load: 10No, 1Phase ,400Watt, starting P.F is 0.7 & running P.F is 0.8, Continuous use.
- Linear Load =General Electrical equipment, Heater
- Non-Linear Load = UPS, Inverter, Ballast, Drives
CALCULATION:
LOAD NO:1 (MOTOR LOAD)
- Total Load (KW)= No of Equipment X Size of Equipment
- Total Load (KW)=01×90 =90KW
- Diversify Load (KW)= Total Load X Duty factor (0=Stand by Load,1=continuous Load, 0 to 1 =Intermediate Load)
- Diversify Load (KW) = 90×1= 90KW————————————–(1)
- Running KVA = Diversify Load (KW) / Running P.F
- Running KVA = 90 x 0.8
- Running KVA =113 KVA————————————–(2)
- Running Amp (Amp) = Diversify Load (KW) / 1.732 x Volt x Running P.F
- Running Amp (Amp) =90×1000 / 1.732 x 415 x 0.8
- Running Amp (Amp) =156.7 Amp
- Starting Amp = Running Amp X Multiplying Factor of Starter
- Multiplying Factor of Starter is as under.
| Starter Starting current | |
| Method | Starting current |
| Direct-on-Line (DOL) | 5 to 10 times the full load current |
| Star-Delta Starter | 3 to 4 times the full load current |
| Auto-transformer | 2 to 3 times the full load current |
| Soft starter | 1.1 to 2 times full load current |
| Variable Speed drive | 1.1 to 1.5 times full load current |
- Considering Multiplying Factor for Soft Starter is 2
- Starting Amp = 156.7 X 2
- Starting Amp =313Amp
- Starting KVA = (Diversify Load (KW) / Starting P.F) X Multiplying Factor of Starter
- Starting KVA = (90/0.7) X 2
- Starting KVA = 257 KVA——————————————–(3)
LOAD NO:2 (HVAC LOAD)
- Total Load (KW)= No of Equipment X Size of Equipment
- Total Load (KW)=01×20 =20KW
- Diversify Load (KW)= Total Load X Duty factor (0=Stand by Load,1=continuous Load, 0 to 1 =Intermediate Load)
- Diversify Load (KW) = 20×0.8= 16KW————————————–(4)
- Running KVA = Diversify Load (KW) / Running P.F
- Running KVA = 16 x 0.8
- Running KVA =20 KVA————————————–(5)
- Running Amp (Amp) = Diversify Load (KW) / 1.732 x Volt x Running P.F
- Running Amp (Amp) =16×1000 / 1.732 x 415 x 0.8
- Running Amp (Amp) =28 Amp
- Starting Amp = Running Amp X Multiplying Factor of HVAC
- Multiplying Factor of Starting Current for various type of Load is as under.
|
Starting current |
|
| Type of Load | Starting current for Load |
| Linear | 1 time the full load current |
| Non-Linear | 1.2 to 1.6 times the full load current |
| HVAC | 1.2 to 1.5 times the full load current |
- Considering Multiplying Factor of HVAC is 1.3
- Starting Amp = 28X 1.3
- Starting Amp =36Amp
- Starting KVA = (Diversify Load (KW) / Starting P.F) X Multiplying Factor of HVAC
- Starting KVA = (16/0.7) X1.3
- Starting KVA = 30 KVA——————————————–(6)
LOAD NO:3 (NON-LINEAR LOAD)
- Total Load (KW)= No of Equipment X Size of Equipment
- Total Load (KW)=01×7 =7KW
- Diversify Load (KW)= Total Load X Duty factor (0=Stand by Load,1=continuous Load, 0 to 1 =Intermediate Load)
- Diversify Load (KW) = 7×1= 7KW————————————–(7)
- Running KVA = Diversify Load (KW) / Running P.F
- Running KVA = 7 x 0.8
- Running KVA =9 KVA————————————–(8)
- Running Amp (Amp) = Diversify Load (KW) / 1.732 x Volt x Running P.F
- Running Amp (Amp) =7×1000 / 1.732 x 415 x 0.8
- Running Amp (Amp) =12 Amp
- Starting Amp = Running Amp X Multiplying Factor of Non-Linear Load
- Multiplying Factor of Starting Current for various type of Load is as under.
|
Starting current |
|
| Type of Load | Starting current for Load |
| Linear | 1 time the full load current |
| Non-Linear | 1.2 to 1.6 times the full load current |
| HVAC | 1.2 to 1.5 times the full load current |
- Considering Multiplying Factor of Non-Linear Load (UPS) is 1.6
- Starting Amp = 12X 1.6
- Starting Amp =19Amp
- Starting KVA = (Diversify Load (KW) / Starting P.F) X Multiplying Factor of HVAC
- Starting KVA = (7/0.7) X1.6
- Starting KVA = 16 KVA——————————————–(9)
LOAD NO:4 (LINEAR LOAD)
- Total Load (KW)= No of Equipment X Size of Equipment
- Total Load (KW)=10×0.4 =4KW
- Diversify Load (KW)= Total Load X Duty factor (0=Stand by Load,1=continuous Load, 0 to 1 =Intermediate Load)
- Diversify Load (KW) = 4×1= 4KW————————————–(10)
- Running KVA = Diversify Load (KW) / Running P.F
- Running KVA = 4 x 0.8
- Running KVA =5 KVA————————————–(11)
- Running Amp (Amp) = Diversify Load (KW) / 1.732 x Volt x Running P.F
- Running Amp (Amp) =4×1000 / 230 x 0.8
- Running Amp (Amp) =22 Amp
- Starting Amp = Running Amp X Multiplying Factor of Linear Load
- Multiplying Factor of Starting Current for various type of Load is as under.
|
Starting current |
|
| Type of Load | Starting current for Load |
| Linear | 1 time the full load current |
| Non-Linear | 1.6 times the full load current |
| HVAC | 1.2 to 1.5 times the full load current |
- Considering Multiplying Factor of Linear Load is 1
- Starting Amp =22×1
- Starting Amp =22Amp
- Starting KVA = (Diversify Load (KW) / Starting P.F)
- Starting KVA = (4/0.7)
- Starting KVA = 6 KVA——————————————–(12)
TOTAL LOAD CALCULATION:
- Total Starting KVA= Starting KVA of (Load 1+ Load 2+ Load 3 +Load 4)
- Total Starting KVA= 257+30+16+6
- Total Starting KVA= 309 KVA————————————(A)
- Total Running KVA =Running KVA of (Load 1+ Load 2+ Load 3 +Load 4)
- Total Running KVA =113+20+9+5
- Total Running KVA = 146 KVA—————————–(B)
- D.G set Size (KVA) = Total Starting KVA x Future Load Expansion.
- D.G set Size (KVA) = 309×1.1 (10% Future expansion)
- D.G set Size (KVA) = 339 KVA—————————————-(C)
CONDITION FOR SELECTING D.G SET:
- CONDITION-1:
- Total Non-Linear Load < 30% of D.G Size
- Here Value no (9) < Value no (C)
- 16 KVA < 102 KVA
- Condition-1 is full fill
- CONDITION-2:
- Overloads withstand Capacity of D.G > Total Required starting KVA
- Overload withstand capacity of D. G= D.G size X D.G over Load Capacity
- Overload withstand capacity of D. G= 339 x 130%
- Overload withstand capacity of D. G= 401 KVA——————–(D)
- Total Required starting KVA = Total Load (KVA) -Largest Motor rating (KVA)+ Largest Motor starting (KVA)
- Total Required starting KVA =146 -113+257
- Total Required starting KVA =291 KVA ————————(E)
- Here Value no (D) > Value no (E)
- 401 KVA > 291 KVA
- Condition-2 is full fill
CONCLUSION:
- Here Condition-1 & Condition-2 is full fill hence selected D.G Size is OK.
- Hence D.G size is 339 KVA or near its 380 KVA




Recent Comments