Quick Reference-Fire Fighting (Part-3)
August 15, 2021 2 Comments
Pipe Support Details |
|||
Nominal Pipes Diameter |
Hanger rod diameter |
Hanging Strip Size(thickxwidh) |
Spacing between supports |
25 mm |
8 mm |
20 x 1 mm |
2 Meter |
32 mm |
8 mm |
20 x 1 mm |
2.5 Meter |
40 mm |
8 mm |
20 x 1 mm |
2.5 Meter |
50 mm |
10 mm |
25 x 1.2 mm |
2.5 Meter |
65 mm |
10 mm |
25 x 1.2 mm |
2.5 Meter |
80 mm |
10 mm |
25 x 1.2 mm |
2.5 Meter |
100 mm* |
12 mm |
25 x 1.6 mm |
2.5 Meter |
125 mm* |
12 mm |
25 x 2 mm |
3 Meter |
150 mm* |
12 mm |
25 x 2 mm |
3 Meter |
* As per Site Requirement Fabrication Support may be used. |
Sprinkler Qty |
||
Pipe Size |
Min.Sprinkler Qty |
Max.Sprinkler Qty |
25 mm |
1 |
2 |
32 mm |
3 |
4 |
40 mm |
5 |
7 |
50 mm |
8 |
15 |
65 mm |
16 |
30 |
80 mm |
31 |
60 |
100 mm* |
61 |
100 |
150 mm* |
More than 100 |
Supporting Chanel & U Bolt |
||
Pipe Size |
Chanel |
U Bolt Dia |
Up to 50 mm |
38x38xx6 mm |
9 mm |
65 To 100 mm |
75x75x6 mm |
12 mm |
125 To 200 mm |
88x88x9 mm |
15 mm |
Flange Details |
||
Pipe Dia |
Flange Thickness |
No. of holes |
200 mm. |
24 mm. |
12 |
150 mm and 125 mm |
22 mm. |
8 |
100 mm and 80 mm |
20 mm. |
8 |
65 mm. |
18mm |
4 |
40 mm and below. |
16mm |
4 |
Pipe Support Details |
||
MS Angle(mm) |
Anchor Faster |
Width |
40X40X5 |
12MM |
200MM both Side of Pipe |
Holiday Test Voltage (IS 15337) |
|
Thickness of Coating |
Test Voltage, Max |
2 mm |
10KV |
3 mm |
12KV |
4 mm |
15KV |
Recommended Welding Electrode Size |
||
Average Thickness of Plate or Sections |
Maximum Electrode Size |
Current Range |
1.5 To 2.0 mm |
2.5 mm |
60 To 95 Amp |
2.0 To 5.0 mm |
3.2 mm |
110 To 130 Amp |
5.0 To 8.0 mm |
4.0 mm |
140 To 165 Amp |
>8.0 mm |
5.0 mm |
170 To 260 Amp |
Recent Comments