Minimum Clearance in Substation:
| Voltage |
Highest Voltage |
Lighting Impulse Level (Kvp) |
Switching Impulse Level (Kvp) |
Minimum Clearance |
Safety Clearance(Mt) |
Ground Clearance(Mt) |
| Phase-Earth |
Phase-Phase |
| 11KV |
12KV |
70 |
|
0.178 |
0.229 |
2.600 |
3.700 |
| 33KV |
36KV |
170 |
|
0.320 |
0.320 |
2.800 |
3.700 |
| 132KV |
145KV |
550 |
|
1.100 |
1.100 |
3.700 |
4.600 |
| 650 |
|
1.100 |
1.100 |
2.700 |
4.600 |
| 220KV |
245KV |
950 |
|
1.900 |
1.900 |
4.300 |
5.500 |
| 1050 |
|
1.900 |
1.900 |
4.300 |
5.500 |
| 400KV |
420KV |
1425 |
1050(P-E) |
3.400 |
4.200 |
6.400 |
8.000 |
Electrical Clearance in Substation:
| Voltage |
Height of I Bay From Ground (Mt) |
Height of II Bay From Ground (Mt) |
Bay Width (Mt) |
Phase-Phase (Mt) |
BetweenEquipment |
Earth Wire From Ground |
| 132KV (Single) |
8.0 |
– |
11.0 |
3.0 |
3.0 |
10.5 |
| 220KV (Single) |
12.5 |
– |
18 |
4.5 |
4.5 |
15.5 |
| 220KV (Double) |
18.5 |
25 |
25 |
4.5 |
4.5 |
28.5 |
| 400KV |
15.6 |
22 |
22.0 |
7.0 |
>6.0 |
30.0 |
Standard Bay Widths in Meters:
| Voltage |
Bay Width (Meter) |
| 11KV |
4.7 Meter |
| 33KV |
4.7 Meter |
| 66KV |
7.6 Meter |
| 132KV |
12.2 Meter |
| 220KV |
17 Meter |
| 400KV |
27 Meter |
Standard Bus and Equipment Elevation
| Voltage |
Equipment live Terminal Elevation (Meter) |
Main Bus |
Take of Elevation (Meter) |
| Low |
High |
| 11 KV/33KV |
2.8To 4 |
5.5 To6.5 |
9 |
6.5To8.5 |
| 66KV |
2.8To 4 |
6To8 |
9To 10.5 |
9.5 |
| 132KV |
3.7To5 |
8To9.5 |
13.5To14.5 |
12To12.5 |
| 220KV |
4.9To5.5 |
9To13 |
18.5 |
15To18.5 |
| 400KV |
8.0 |
15.5 |
– |
23 |
Phase spacing for strung Bus:
| Voltage |
Clearance |
| 11KV |
1300 mm |
| 33KV |
1300 mm |
| 66KV |
2200 mm |
| 132KV |
3000 mm |
| 220KV |
4500 mm |
| 400KV |
7000 mm |
Minimum Clearance of Live Parts from Ground:
| Voltage |
Minimum Clearance to Ground (Mt) |
Section Clearance (Mt) |
| 11KV |
3.700 |
2.600 |
| 33KV |
3.700 |
2.800 |
| 66KV |
4.600 |
3.000 |
| 132KV |
4.600 |
3.500 |
| 220KV |
5.500 |
4.300 |
| 400KV |
8.000 |
7.000 |
Insulator String:
| Voltage |
No of Suspension String |
Length (mm) |
No of Disc for Tension String |
Length in (mm) |
| 66KV |
5 |
965 |
6 |
1070 |
| 132KV |
9 |
1255 |
10 |
1820 |
| 220KV |
14 |
1915 |
15 |
2915 |
| 400KV |
23 |
3850 |
2 X 23 |
5450 |
Nominal Span:
| Voltage |
Normal Span (Meter) |
| 66KV |
240-250-275 |
| 132KV |
315-325-335 |
| 220KV |
315-325-335 |
| 400KV |
315-325-335 |
Minimum Ground Clearance:
| Voltage |
Ground (Meter) |
| 66KV |
5.5 |
| 132KV |
6.1 |
| 220KV |
7.0 |
| 400KV |
8.0 |
| 800KV |
12.4 |
Indoor Substation Minimum Clearances
| Distance |
Descriptions |
| 0.9 Meter |
Horizontally between any item of equipment and thesubstation wall |
| 0.6 Meter |
Horizontally between any Two items of equipment |
| 1.2 Meter |
Horizontally in front of any HV switchgear |
Clearance of Conductor on Tower
| Voltage |
Tower Type |
Vertical Space (Mt) |
Horizontal Space(Mt) |
Total Height From Ground(Mt) |
| 66KV |
A |
1.03 |
4.0 |
15.91 |
| |
B |
1.03 |
4.27 |
15.42 |
| |
C |
1.22 |
4.88 |
16.24 |
| 132KV |
A |
7.140 |
2.17 |
23.14 |
| |
B |
4.2 |
6.29 |
22.06 |
| |
C |
4.2 |
7.15 |
22.68 |
| |
D |
4.2 |
8.8 |
24.06 |
| 220KV |
A |
5.2 |
8.5 |
28.55 |
| |
B |
5.25 |
10.5 |
29.08 |
| |
C |
6.7 |
12.6 |
31.68 |
| |
D |
|
|
|
NORMS OF PROTECTION FOR EHV CLASS POWER TRANSFORMERS
| Voltage ratio & capacity |
HV Side |
LV Side |
Common relays |
| 132/33/11KV up to 8 MVA |
3 O/L relays + 1 E/L relay |
2 O/L relays + 1 E/L relay |
Buchholz, OLTC Buchholz, OT, WT |
| 132/33/11KV above 8 MVA and below 31.5 MVA |
3 O/L relays + 1 dir. E/L relay |
3 O/L relays + 1 E/L relay |
Differential, Buchholz, OLTC Buchholz, OT, WT |
| 132/33KV, 31.5 MVA & above |
3 O/L relays + 1 dir. E/L relay |
3 O/L relays + 1 E/L relay |
Differential, Over flux,Buchholz, OLTC PRV, OT, WT |
| 220/33 KV, 31.5MVA & 50MVA 220/132KV, 100 MVA |
3 O/L relays + 1 dir. E/L relay |
3 O/L relays + 1 dir. relay |
Differential, Over flux,Buchholz, OLTC PRV, OT, WT |
| 400/220KV 315MVA |
3 directional O/L relays (with dir. High set) +1 directional E/L relays. Restricted E/F relay + 3 Directional O/L relays for action |
3 directional O/L relays (with dir. High set)+1 directional E/L relays. Restricted E/F relay |
Differential, Over flux,Buchholz, OLTC PRV, OT, WT and overload (alarm) relay |
The bottom most portion of any insulator or bushing in service should be at a minimum height of 2500 mm above ground level.
Location of L.A (From T.C Bushing):
| Voltage |
BIL KV Peak |
Distance (Mt) |
| 11KV |
75 |
12 |
| 33KV |
200 |
15 |
| 66KV |
325 |
24 |
| 132KV |
550 |
35 |
| 220KV |
900 To 1050 |
Close To T.C |
| 400KV |
1425 To 1550 |