Calculate Size of Lift Pressurization Fan for Highrise Building
June 22, 2025 1 Comment
Calculate Size Lift Well Pressurization Fan having following Details
- Type of Building is Commercial and Sprinkler Protected
- Number of Lift Door (Basement to Terrace) is 17 Nos (B+G+15)
- Lift Shaft width is 3600mm and Length is 3600mm
- Lift Shaft height is 45 Meter
- Vent window Size at Top of Lift Shaft is 320mm to 320mm
- Lift Door width is 1 meter and Height is 1.2 meter.
- No of Lift Door is 17 Nos
- No of Floor door (Single Leaf) is 26 Nos
- Air Velocity across door is 0.75 m/sec
Calculation:
- Air Leakage are calculated on following areas
- Leakages through Door on each Floor
- Leakages through lift Doors, Shafts, Vents
- Leakages through External Wall, Floors
- Open Lift Door
(1) Leakages through Door on each Floor
- No of Floor door (Single Leaf) is 26 Nos
- Leakage Area around the Door as per BS:5588 = 0.01m2
|
Air Leakage Data for Doors (BS 5588: Part-4) |
|
|
Type of Door |
Leakage Area (m2) |
|
Single Leaf Doors in Frame Opening into Pressurized Space |
0.01 |
|
Single Leaf Doors in Frame Opening Outwards |
0.02 |
|
Double Leaf Doors with or without Central Rebate |
0.03 |
|
Lift Door |
0.06 |
- Total leakage area all doors on all floors (A1): No of Door x Leakage area around Door
- Total leakage area all doors on all floors (A1):26 x 0.01
- Total leakage area all doors on all floors (A1):0.26 m2
(2) Leakages through lift Doors, Shafts, Vents
(a) Leakage through Lift Shaft:
- Lift Shaft Wall Perimeter = 2 x (Lift Shaft Width + Lift Shaft Length)
- Lift Shaft Wall Perimeter =2 x (3.6+3.6)
- Lift Shaft Wall Perimeter =14.4 Meter
- Leakage Area through Lift Shaft = Lift Shaft Perimeter x Lift Shaft Height
- Leakage Area through Lift Shaft =14.4 x 45
- Leakage Area through Lift Shaft =648.8 Meter
- Leakage Area Ratio for Lift Shaft: (A/Aw) =0.00084 as per NFPA 92A
|
Typical Leakage Area for Walls & Floors for Commercial Buildings (NFPA-92A) |
||
|
Construction |
Wall Tightness |
Area Ratio |
|
Exterior Building Wall (Including Construction Cracks but not around window & doors) |
Tight |
0.00005 |
|
Average |
0.00017 |
|
|
Loose |
0.00035 |
|
|
Very Loose |
0.0012 |
|
|
Staircase Wall (Including Construction Cracks but not around window & doors) |
Tight |
0.000014 |
|
Average |
0.00011 |
|
|
Loose |
0.00035 |
|
|
Lift Shaft Wall (Including Construction Cracks but not around window & doors) |
Tight |
0.00018 |
|
Average |
0.00084 |
|
|
Loose |
0.0018 |
|
|
Floor (Including Construction Cracks but not around window & doors) |
Tight |
0.0000066 |
|
Average |
0.000052 |
|
|
Loose |
0.00017 |
|
- Effective leakage Area (a)= Leakage Area Ratio for Lift Shaft x Leakage Area through Lift Shaft.
- Effective leakage Area (a)= 0.00084 x 648.8
- Effective leakage Area (a)=0.544 m2
(b) Leakages through Lift doors
- No of Lift Door =17 Nos
- Leakage Area around the Lift Door as per BS:5588 = 0.06m2
- Leakage area around lift doors (b): No of Lift Door x Leakage around Lift Door
- Leakage area around lift doors (b): 17 x 0.06
- Leakage area around lift doors (b): 1.020 m2
(c) Leakage through Vent at the head of the shaft
- Vent Window Area (At the head of the shaft)(c) = Vent window width x Vent window height
- Vent Window Area (At the head of the shaft) (c) = 0.320 x 0.320
- Vent Window Area (At the head of the shaft) (c) =0.102
- Total Leakage Area (A2) = (a)+(b)+(c)
- Total Leakage Area (A2) = 0.544+1.020+0.102
- Total Leakage Area(A2) =1.667 m2
- Effective Leakage Area (Ae)= A1 x A2 / (A12 + A22)0.5
- Effective Leakage Area (Ae)= 0.26 x 1.667 / (0.26 + 1.667) 0.5
- Effective Leakage Area (Ae)= 0.257 m2
(4) Open Lift Doors
- No of Open Lift Door = 2 Nos
- Lift Door Area = Lift Door Width x Lift Door Height
- Lift Door Area = 1.0 x 1.2
- Lift Door Area =2.2 m2
- Open Lift Door Area = No of Open Lift Door x Lift Door Area
- Open Lift Door Area = 2 x 2.2
- Open Lift Door Area = 4.4 m2
- Velocity through Open Door = 0.75 meter/sec (*As per BS 5588: Part-4)
- Air Flow through open doors = Air Velocity x Open Lift Door Area
- Air Flow through open doors = 0.75 x 4.4
- Air Flow through open doors =3.3 m3/sec
Calculate Air Flow for Lift well Pressurization
- Air Flow for Lift Well Pressurization = 0.839 x Ae x (ΔP)1/2
- Minimum Design Pressure difference for Lift well pressurization (ΔP) = 50pa (*As per BS 5588)
- Minimum Design Pressure difference for Lift well pressurization (ΔP) = 50pa (*As per NBC 2016)
- Minimum Design Pressure difference for Lift well pressurization (ΔP) = 10pa (*As per NFPA 92A)
- Consider Design Pressure difference for Lift well pressurization (ΔP) = 50pa
|
The pressure difference AS per NBC-2016 (Clause 4.4.2.5) |
|
|
Enclosed Lobbies (or corridors) |
25 to 30 Pa |
|
Lift Shaft |
50 Pa |
|
Staircases |
50 Pa |
|
Enclosed staircase adjacent to such lobby (or corridors) |
50 Pa |
|
Enclosed staircases adjacent to non-pressurized lobby (or corridors) |
50 Pa |
|
Minimum Design Pressure difference (BS 5588: Part-4) |
|||
|
Type |
Building |
Air Flow through Door way |
Minimum Design Pressure difference |
|
A |
Residential or Sheltered House or Building having Three Door Protection |
0.75 Meter/Sec |
50 Pa |
|
B |
Protection of Fire Shaft |
2.00 Meter/Sec |
50 Pa |
|
C |
Commercial Premises |
0.75 Meter/Sec |
50 Pa |
|
D |
Hotels or Institutional Type Building |
0.75 Meter/Sec |
10 Pa |
|
Minimum Design Pressure difference (NFPA-92A, Table:4.4.2.1.1) |
||
|
Type of Building |
Ceiling Height |
Minimum Design Pressure difference |
|
Sprinklered |
Any |
12.5 Pa |
|
Non Sprinklered |
2.75 Meter |
25.0 Pa |
|
Non Sprinklered |
4.58 Meter |
35.0 Pa |
|
Non Sprinklered |
6.41 Meter |
45.0 Pa |
- Air Flow for Lift Well Pressurization = 0.839 x 0.257 x (50)1/2
- Air Flow for Lift Well Pressurization = 1.508 m3/sec
- Total Air Flow for Lift Well Pressurization = Air Flow for Lift Well Pressurization+ Air Flow through open doors
- Total Air Flow for Lift Well Pressurization = 1.508 + 3.3
- Total Air Flow for Lift Well Pressurization = 4.8 m3/sec
- Consider Safety Factor =10 %
- Total Air Flow for Lift Well Pressurization = 4.8 x 1.1
- Total Air Flow for Lift Well Pressurization =5.288 m3/Sec
- Total Air Flow for Lift Well Pressurization =5.288 x 2118.88
- Total Air Flow for Lift Well Pressurization =11206 CFM
Conclusion:
- Capacity of Lift Well Pressurization Fan = 11206 CFM