Minimum Acceptable Specification of C.T & P.T for Metering


Min. Acceptable Specification of Current Transformer for Metering:

Sr. No Particulars 11 kV 33 kV 132 kV 220 kV 
1 Highest System Voltage (kV rms) 12 36 145 245
2 CT ratio. 2000-1000/1-1 800-400/1-1 400/1-1 800/1-1
1600-800/1-1 600-300/1-1    
1200-600/1-1 400-200/1-1    
800-400/1-1 300-150/1-1    
600-300/1-1 100-50/1-1    
400-200/1-1      
300-150/1-1      
150-75/1-1      
3 Number of metering cores Two Nos Two Nos Two Nos Two Nos
4 Rated continuous thermal current. 120% of rated primary  current 120% of rated primary  current 120% of rated primary  current 120% of rated primary  current
5 Rated short time thermal current of primary for 1 sec. (kA) 25 25 31.5 40
6 CT characteristics :a) Rated primary current (Amps.)  2000-1000  800-400  400  800
1600-800 600-300    
1200-600 400-200    
800-400 300-150    
600-300 100-50    
400-200      
300-150      
150-75      
(b) Rated Secondary current (Amps.) 1 1 1 1
(c) Class of accuracy. 0.2 0.2 0.2 0.2
(d) Max. instrument security factor 5 5 5 5
(e) Rated burden (VA). 30 30 30 40
7 IS to which CT conforms.        
8 IS to which insulating oil conforms.        

 Min. Acceptable Specification of Voltage Transformer for Metering:

Sr. No Particulars     245 kV CVTs      145 kV CVTs 
1 Highest SystemVoltage (kV)          245 kV              145 kV
2 Rated Capacitance (pF)  4400 pf with tolerance + 10% and – 5%
3 For low voltage terminal over entire carrier frequency range.    
  (a) Stray capacitance  Shall not exceed 200 pf
  (b) Stray conductance Shall not exceed 20 us
4 (a) High frequency            capacitance for entirecarrier frequency range within 80% to 150% of rated capacitance
  (b) Equivalent series resistance over the entire frequency range. less than 40 Ohms
5 No. of secondary windings for potential device.             Two              Two
6 Transformation ratio:  
  (i) Winding –I   20 kV- \/3/110 -\/3V
  (ii) Winding –II   20 kV- \/3/110 -\/3V
7 Rated secondary burden    
  (i)Winding –I   (VA) 50 VA 50 VA
  (ii) Winding –II  (VA) 50 VA 50 VA
8 Accuracy Class :    
  (i)Winding –I   (VA)                        0.2 for metering
  (ii) Winding –II  (VA)                        0.2 for metering
9 Voltage factor for winding – IVoltage factor for winding – II 1.2 Cont. & 1.5 for 30 secs.1.2 Cont. & 1.5 for 30 secs.
10 IS to which CVTs conform. IS 3156 with latest amendment
11 IS to which Insulating Oil conform. IS 335 with latest amendment
     

Minimum Acceptable Specification of Single Phase PT for Metering:

Sr.No Particulars        33 kV         11 kV 
1 Highest System Voltage (kV rms)           36             12
2 Transformation ratio.   33kV/ V3/     110/ V3   11 kV/110 V
3 Number of windings.          Two           Two
4 Rated output/ burden (VA) per winding /phase.           50             50
5 Accuracy class. (At 10 to 100% of VA burden)          0.2             0.2
6 Rated voltage factor and duration. 1.2 continuous & 1.5 for 30 secs.
7 IS to which PT conforms.   3156 with latest amendment