Calculate Diesel Generator Protection Setting


Recommended Generator Protection are

Recommended Generator Protection

ANSI Code

Protection Function

27

Under Voltage

32

Reverse Power
37

Under Power

40

Loss of Excitation
46

Negative Phase Sequence /Un Balance Load

49T

Thermal Overload
50

Instantaneous Over Current

51

Time grade Over Current
51G

Earth Fault Time Overcurrent

50/51V

Voltage Restrained Overcurrent
59

 Over voltage

60G

 Fuse Failure Monitor
64S

Stator Earth Fault Protection

81

Under / Over Frequency
87

Three Phase Current Differential

87N

Neutral Current Differential

87G

Generator Differential Protection

24G

Over excitation (Volt/Hertz) Protection

21G

Impedance Protection
59N or 64G1

Stator EF protection (0-95%)

27TN or 64G2

Stator EF protection (100%)
50BF

Breaker Failure Protection

24G

Over excitation (Volt/Hertz) Protection

78G

Pole slip protection

Protection Setting Calculation:

(1) Under Voltage Relay (27):

  • The Under Voltage Relay measure either phase-to-phase (Ph-Ph) or phase-to-neutral (Ph-N) fundamental RMS voltage depending on the input voltage setting. If the value of measured voltages deviates from the setting values, then these relays will give a trip indication.
  • Reason:
  • An under-voltage condition in a diesel generator can occur due to several reasons, overloading the generator beyond its capacity, faulty Automatic Voltage Regulator (AVR), issues with the stator windings, problems with the voltage sampling line, loose connections, low engine speed, fuel problems, and issues with the excitation system
  • Setting:
  • The Typical under-voltage setting is usually 80 % of the normal rated voltage. If the voltage falls below this level for the set amount of time, then the tripping command is issued by the relay and hence the system is isolated. The time setting is used to avoid tripping due to any transient disturbances. the exact setting can vary depending on the specific generator and system requirements.
  • Usually, motors stall at below 80% of their rated voltage. An under-voltage element can be set to trip motor circuits once fall below 80% so that on the restoration of supply an overload is not caused by the simultaneous starting of all the motors.
  • Normally Generators are designed to operate continuously at minimum voltage of 95% of its rated voltage.
  • Two levels of tripping are provided depending on the severity of the condition, these under voltage elements are blocked from tripping when the generator breaker is open to allow for startup conditions.
  • Calculation:
  • For 415V Diesel Generator
  • Level 1 (Slow)= 80% of Rated Voltage
  • Level 1 (Slow)= 80% x 415V =332 V
  • Time Delay = 5 sec.
  • Level 2 (Fast): 70% of Rated Voltage
  • Level 2 (Fast)= 70% x 415V =290 V
  • Time Delay = 0 sec.

(2) Over Voltage Protection [59]:

  • The Over Voltage Relay measure either phase-to-phase (Ph-Ph) or phase-to-neutral (Ph-N) fundamental RMS voltage depending on the input voltage setting. If the value of measured voltages deviates from the setting values, then these relays will give a trip indication.
  • Reason:
  • System over voltages can damage the insulation of components. Over voltages occur due to sudden loss of load, improper working of tap changer, Generator AVR malfunction, Reactive component malfunctions, etc.
  • Setting:
  • The Overvoltage setting is usually 110 to 130 % of the normal operating voltage depending on the system requirement.
  • If the voltage rises above this level for the set amount of time then the tripping command issued by the relay and hence the system is isolated. The time setting is used to avoid tripping due to any transient disturbances.
  • Calculation:
  • For 415V Diesel Generator
  • Level 1 (Slow)= 110% of Rated Voltage
  • Level 1 (Slow)= 110% x 415V =456 V
  • Time Delay = 5 sec.
  • Level 2 (Fast): 130% of Rated Voltage
  • Level 2 (Fast)= 130% x 415V =539 V
  • Time Delay = 0 sec.

(3) Reverse Power Protection [32R]:

  • Reverse power relay is an electronic, microprocessors-based protection device which is used for monitoring and stopping the power supply flowing grid side to the DG side or generator running in parallel with another generator. If accidentally leakage current is received by generator, then it can start to running as motor. This situation may be very dangerous for generator set.
  • The function of the reverse power relay is to prevent a reverse power condition in which power flows from the bus bar into the generator.
  • This condition can occur when there is a failure in the prime mover such as an engine or a turbine which drives the generator.
  • Relay detects the reverse flow of power from the load back to the generator, which can occur during system faults or abnormal operating conditions. By sensing this reverse power flow, the relay triggers a protective action, typically disconnecting the generator to prevent further issues.
  • The generator are classified by their Prime Mover which determine the amount of Reverse power they can motor.
Sr. No Prime Mover Motorizing Power in % of Unit Rating
1 Gas Turbine (single shaft) 100%
2 Gas Turbine (Double Shaft) 10-15%
3 4 Cycle Diesel 15%
4 2 Cycle Diesel 25%
5 Hydraulic Turbine 2-100
6 Steam Turbine (Conventional) 1-4%
7 Steam Turbine (Cond Cooled) 0.5 to 1.0%
  • Reason:
  • When Two or more unit running in parallel
  • In LT panel if the DG supply is running then grid supply should be switched off and if the grid supply is running then DG supply should be switched off. When one source is on then second source accidentals starts to leakage current resultant a large fault may be occurred and system can be failed. So, for prevention of other source leakage the RPR relay is used.
  • Failure of Speed controller or another breakdown. When the prime mover of a generator running in a synchronized condition fails. There is a condition known as motoring, where the generator draws power from the bus bar, runs as a motor and drives the prime mover. This happens as in a synchronized condition all the generators will have the same frequency. Any drop in frequency in one generator will cause the other power sources to pump power into the generator. The flow of power in the reverse direction is known as the reverse power relay.
  • If the frequency of the machine to be synchronized is slightly lesser than the bus bar frequency and the breaker is closed, power will flow from the bus bar to the machine. Hence, during synchronization(forward), frequency of the incoming machine is kept slight higher than that of the bus bar i.e. the synchroscope is made to rotate in the “Too fast” direction. This ensures that the machine takes on load as soon as the breaker is closed.
  • Loss of excitation:
  • Failure of AVR
  • Setting:
  • A generator reverse power relay setting is typically set between 2% to 8% of the generator’s rated power, depending on the type of prime mover (like a diesel engine or steam turbine), with diesel engines generally requiring a higher setting (around 8%) compared to turbines (around 2 to 5%) to prevent unnecessary tripping during transient conditions; this setting essentially determines the threshold at which the relay will activate to protect the generator from reverse power flow, which can damage the machine if it becomes too significant. 
  • Calculation:
  • Generator capacity :500KVA ,415V,0.9 Power factor
  • Full Load Current =500×1000/(1.732*415)
  • Full Load Current =695A
  • Setting at 5%
  • Reverse Power = -5%*500*0.9 = -22.5KW
  • Relay Setting= Reverse Power / Real Power =-22.5 / 500 =-4.50%
  • Relay Setting =-4.50%
  • Time delay proposed=5 sec

(4) Negative Phase Sequence (Unbalance Phase) Relay (46):

  • The Negative Sequence Overcurrent function provides protection against possible rotor overheating and damage due to unbalanced faults or other system conditions which can cause unbalanced three phase currents in the generator.
  • Negative Phase Sequence detects imbalances in the network that does not cause energy loss out of the system.
  • Reason:
  • Generator or Motor are design to operate in balance three phase loading.
  • Generator negative phase sequence currents can result from any unbalance condition on the system including un transposed lines, single phase loads, unbalanced type line faults and open conductors. the unbalance condition leads negative sequence currents having opposite rotation that of power system in generator leads. This reversed rotating current produce double frequency current in rotor structure. This resulting over heating of rotor.
  • Setting:
  • A generator Negative Phase Sequence (NPS) relay setting is typically set between 2 to 10% of the full load current depending on the specific generator design and manufacturer’s recommendations, aiming to detect significant unbalances in the power system while avoiding unnecessary tripping due to normal load variations; this setting should be based on the generator’s maximum allowable negative sequence I² (current squared) value to prevent excessive rotor heating. 
  • Generator withstand limit against negative sequence overcurrent (K) = 10 (As per IEC-60034-1)
  • Normally Generator continuous withstand limit: 8 %
  • Calculation:
  • Generator capacity :500KVA ,415V , CT is 800/1
  • Full Load Current =500×1000/(1.732*415)
  • Full Load Current =695A
  • Setting at 10% .
  • Desired pickup current = 10% of rated current
  • Relay setting = (0.1 x Rated Current) / CT ratio 
  • Relay setting =(0.1×695) / 800
  • Relay setting =0.0868A

(5) Thermal Overload Relay (49T):

  • In general, generators can operate successfully at rated kVA, frequency, and power factor for a voltage variation of 5% above or below rated voltage. Under emergency condition, it is possible to exceed the continuous output capability for a short time.
  • The stator overload function provides protection against possible damage during overload conditions.
  • Reason:
  • A generator becomes overloaded when too many appliances or devices are plugged in and drawing power simultaneously, exceeding the generator’s rated capacity, often happening when attempting to power heavy appliances like air conditioners, heaters, or electric stoves at the same time; essentially, drawing more power than the generator can supply. 
  • Peak usage times: Running multiple high-power appliances simultaneously. 
  • Damaged components: Faulty electrical components within the generator can contribute to overload issues. 
  • Improper load management: Not prioritizing which appliances to run on the generator. 
  • Adding new equipment: Plugging in additional appliances without considering the generator’s capacity. 
  • Setting:
  • A generator thermal overload relay setting is typically based on a percentage of the motor’s full load current.
  • Common settings are:
  • For motors with Service Factor (SF) ≥ 1.15, Set to 125% of FLA.
  • For motors with Service Factor (SF) < 1.15, Set to 115% of FLA
  • As per IEEE Generator short time thermal capability for balanced three-phase loading diagram (Short time capability curve) the wining will withstand 117% rated current for 120 second.
  • Calculation:
  • Generator capacity :500KVA ,415V , CT is 800/1
  • Full Load Current =500×1000/(1.732*415)
  • Full Load Current =695A
  • Setting at 117% .
  • Desired pickup current = 117% of rated current
  • Relay setting = (1.17 x Rated Current) / CT ratio 
  • Relay setting =(1.17×695) / 800
  • Relay setting =1.016A

(6) Generator Under Frequency Protection (81 G):

  • Prevents the steam turbine and generator from exceeding the permissible operating time at reduced frequencies.
  • Ensures that the generating unit is separated from the network at a preset value of frequency.
  • Prevent over fluxing (v/f) of the generator (large over fluxing for short times).
  • The stator under frequency relay measures the frequency of the stator terminal voltage.
  • Setting Recommendations:
  • within 0.2 to 0.5Hz below the nominal frequency
  • For Alarm: 48.0 Hz, 2.0 Sec. time delay. 
  • For Trip: 47.5 Hz, 1.0 Sec. or as recommended by Generator Manufacturers.

(7) Instantaneous Over Current Relay (50):

  • Instantaneous overcurrent protection is where a protective relay initiates a breaker trip based on current exceeding a pre-programmed “pickup” value for any length of time. 
  • Setting:
  • A generator phase instantaneous overcurrent relay setting is typically set between 2 to 1.5 times the full load current (FLA) of the generator, ensuring quick tripping in case of a severe fault while avoiding unnecessary trips due to momentary current surges during starting or load fluctuations; this setting is usually referred to as the “pickup current” of the relay. 
  • This is back up protection for Generator. To avoid unnecessary trip of the generator we recommend making OFF this function in generator protection.
  • Calculation:
  • Generator full Load Current = 130A & CT is 300/5 =60
  • Setting =1.5 times of Full Load Current
  • Setting= 1.5×130 =195A
  • 51 Current Setting = Setting / CT Ratio = 195/60 =3.25A.
  • Time setting =5 Second.
  • The proposed above setting is coordinated with other O/C protection setting.

(8) Time grade Over Current Relay (51):

  • Time overcurrent protection is where a protective relay initiates a breaker trip based on the combination of overcurrent magnitude and overcurrent duration, the relay tripping sooner with greater current magnitude. This is a more sophisticated form of overcurrent protection than instantaneous.
  • Setting:
  • This is back-up protection of the generator, for better time gradings the overcurrent setting should be co-ordinate with load connected feeder overcurrent setting.
  • A generator Phase Overcurrent (51) setting is typically set between 125% and 150% of the generator’s full load current, however, the exact setting depends on the specific application and should be coordinated with other system protections.
  • Calculation:
  • Generator full Load Current = 130A & CT is 300/5 =60
  • Setting =150% of Full Load Current
  • Setting= 1.5×130 =195A
  • 51 Current Setting = Setting / CT Ratio = 195/60 =3.25A.
  • Time setting =5 Second.
  • The proposed above setting is coordinated with other O/C protection setting.

(9) Earth Fault Time Overcurrent (51G)

  • This is back-up protection in Earth Fault of generator, for better time gradings the overcurrent setting should be co-ordinate with load connected feeder setting.
  • Setting:
  • Earth Fault Relay setting shall be 10 to 20 % Full Load Current
  • Calculation:
  • Generator full Load Current = 130A & CT is 300/5 =60
  • Setting =20% of Full Load Current
  • Setting= 0.2×130 =26A
  • 51G Current Setting = Setting / CT Ratio = 26/60 =0.43A.
  • Time setting =5 Second.
  • The proposed above setting is coordinated with other O/C protection setting.

(9) Ground Differential (87 N)

  • The ground differential element (87N) that operates based on the difference between the measured neutral current and the sum of the three-phase current inputs.
  • The 87N element provides sensitive ground fault detection on resistance-grounded particularly where multiple generators are connected directly to a load bus.
  • The relay provides two definite-time delayed ground current differential elements designed to detect ground faults on resistance grounded generator.
  • The relay uses the neutral CT connected to the relay input to measure the generator neutral current. It then calculates the residual current, which is the sum of the three phase current inputs (from CTs located at generator terminals).
  • The relay adjusts the residual current by the ratio of the CTR and CTRN settings to scale the residual current in terms of the secondary neutral current. It then calculates the difference. Normally, under balanced load or external ground fault conditions, the difference current should be zero. In the event of an internal ground fault, the difference current is nonzero. If the difference current magnitude is greater than the element pickup setting, the element picks up and begins to operate the definite time-delay.
  • Setting:
  • Earth Fault Relay setting shall be 10 to 20 % Maximum Ground Fault Current
  • Calculation:
  • Generator grounded through 39.8 Ohms Resistance.
  • Generator rated Voltage=13800V, Current 130A
  • Maximum Earth Fault Current =(138000 / 1.732) / 39.8
  • Maximum Earth Fault Current =7967.4 / 39.8
  • Maximum Earth Fault Current = 200 A
  • 87N pickup current setting = 10% x 200 / CT Ratio
  • 87N pickup current setting = 20 / 60
  • 87N pickup current setting = 0.3
  • 87N Time delay =0.2s

Calculate Short Circuit Current at Sub Panel (End user side)


EXAMPLE:

  • Calculate short circuit current at Electrical Equipment Panel / Distribution Board at end user side.
  • HT Power is received by 11KV RMU and given to 11/0.415KV,1000KVA Transformer by 1 no of 3Cx185 Sq.mm 11KV HT Cable of 25 Meter Length.
  • Resistance and Reactance of HT cable are 0.21 Ώ / KM and 0.1 Ώ / KM
  • Transformer impedance is 6.25%.
  • LT Side of Transformer is connected to Main LT Panel by 8 no of 3.5Cx300 Sq.mm cable of 70 Meter.
  • Resistance and Reactance of 3.5Cx300 Sq.mm, XLPE cable are 0.129 Ώ / KM and 0.071 Ώ / KM.
  • Main LT Panel is connected to Sub Panel-1 by 1 no of 3.5Cx300 Sq.mm cable of 80 Meter.
  • Resistance and Reactance of 3.5Cx300 Sq.mm, XLPE cable are 0.129 Ώ / KM and 0.071 Ώ / KM.
  • Main LT Panel is connected to Sub Panel-2 by 1 no of 3.5Cx95 Sq.mm cable of 80 Meter.
  • Resistance and Reactance of 3.5Cx95 Sq.mm, XLPE cable are 0.409 Ώ / KM and 0.072 Ώ / KM.
  • Calculate Short circuit Current at Sub Panel-1 & Sub Panel-2.

1

CALCUALTION

  • Short Circuit Current is calculated at various points of Power Distribution Networks, At Power Receiving Point (11KV), At Main Panel Point (0.415V) and At Sub Distribution Point (0.415V)

(1) SHORT CIRCUIT CURRENT AT 11 KV PANEL / RMU:

  • Assume that 11KV Side System Fault MVA is 350 MVA.
  • Shor Circuit Current at 11KV System = Fault MVA / 1.732 x System Voltage at Fault Point.
  • Shor Circuit Current at 11KV System = 350 / 1.732 x 11.
  • Shor Circuit Current at 11KV System = 18.37 KA.

 (2) SHORT CIRCUIT CURRENT AT TRANSFORMER:

  • To calculate Short Circuit Current at Transformer Side, First We need to sum Impedance of the system up to Transformer (Impedance of HT Source +Impedance of HT Cable + Impedance of Transformer).
  • Transformer Capacity is 1000 KVA
  • Base MVA = TC Size / 1000
  • Base MVA = 1000 / 1000
  • Base MVA = 1 MVA or
  • Base KVA = 1000 KVA
  • % Impedance of Source = Base MVA x100 / System Fault MVA
  • % Impedance of Source = 1 x100 / 350
  • % Impedance of Source = 0.29 Ώ / KM.
  • CALCULATE % RESISTANCE & REACTANCE OF CABLE ( 185 SQ.MM HT CABLE)
  • % Resistance of Cable =Base KVA (TC Capacity) x Cable Resistance x No of Run x Length of Cable / (System Voltage in KV)²x10.
  • % Resistance of Cable =1000 x 0.21 x 1 x 25 / 11x11x10
  • % Resistance of Cable =0.004339 % Ώ
  • % Reactance of Cable =Base KVA (TC Capacity) x Cable Reactance x No of Run x Length of Cable / (System Voltage in KV)²x10.
  • % Reactance of Cable =1000 x 0.1 x 1 x 25 / 11x11x10
  • % Reactance of Cable =0.002066 % Ώ
  • % Impedance of Cable =√ R² + X²
  • % Impedance of Cable =√ (0.004339) ² + (0.002066) ²
  • % Impedance of Cable =0.00481 % Ώ.
  • Considering 10% Tolerance in Transformer Impedance
  • % Impedance of Transformer = Impedance of Transformer – 10% Variation of Transformer Impedance
  • % Impedance of Transformer = 6.25 -(6.25X10%)
  • % Impedance of Transformer =5.63 % Ώ.
  • Total % Impedance up to Transformer = % Impedance of Source +%Cable Impedance + % Transformer Impedance
  • Total % Impedance up to Transformer = 0.29+0.00481+5.63 % Ώ.
  • Total % Impedance up to Transformer = 5.92% Ώ.
  • Fault KVA on LT Side of Transformer = Base MVA of Transformer x100 / Total % Impedance up to Transformer.
  • Fault KVA on LT Side of Transformer = 1 x100 / 5.92.
  • Fault KVA on LT Side of Transformer = 16.9 KVA.
  • Short Circuit Current at Transformer LT Side= Fault KVA / 1.732 x System Voltage at Fault Point.
  • Short Circuit Current at Transformer LT Side= 16.9 / 1.732 x 0.415
  • Short Circuit Current at Transformer LT Side= 25.32 KA

 (3) SHORT CIRCUIT CURRENT AT MAIN LT PANEL:

  • To calculate Short Circuit Current at Main LT Panel, we need to sum Impedance of the system up to Main LT Panel (Total Impedance up to Transformer LT Side + Impedance of LT Cable).
  • Total % Impedance up to Transformer LT Side= 5.92% Ώ.
  • CALCULATE % RESISTANCE & REACTANCE OF CABLE (300 SQ.MM)
  • % Resistance of Cable =Base KVA (TC Capacity) x Cable Resistance x Length of Cable / (System Voltage in KV)²x10.
  • % Resistance of Cable =1000 x 0.129 x 1 x 70 / 0.415 x 0.415 x10
  • % Resistance of Cable =0.66 % Ώ
  • % Reactance of Cable =Base KVA (TC Capacity) x Cable Reactance x No of Run x Length of Cable / (System Voltage in KV)² x10.
  • % Reactance of Cable =1000 x 0.071 x 8 x 70 / 0.415×0.415×10
  • % Reactance of Cable =0.36 % Ώ
  • % Impedance of Cable =√ R² + X²
  • % Impedance of Cable =√ (0.66) ² + (0.36) ²
  • % Impedance of Cable =0.747 % Ώ.——————————–(B)
  • Total % Impedance up to Main LT Panel = % Impedance up Transformer +%Cable Impedance
  • Total % Impedance up to Main LT Panel = = 5.92+0.747 % Ώ.
  • Total % Impedance up to Main LT Panel = = 6.662% Ώ. ————————–(B)
  • Fault KVA on Main LT Panel= Base MVA x100 / Total % Impedance.
  • Fault KVA on LT Side of Transformer = 1 x100 / 6.662.
  • Fault KVA on LT Side of Transformer = 15.01 KVA.
  • Short Circuit Current at Main LT Panel = Fault KVA / 1.732 x System Voltage at Fault Point.
  • Short Circuit Current at Main LT Panel = 15.01 / 1.732 x 0.415
  • Short Circuit Current at Main LT Panel = 20.88 KA.
  • Short Circuit Current at Main LT Panel = 21 KA

(4) SHORT CIRCUIT CURRENT AT SUB PANEL-1:

  • To calculate Short Circuit Current at Sub Panel-1, We need to sum Total Impedance of the system up to Sub Panel-1 (Total Impedance up to Main LT Panel + Impedance of LT Cable-1).
  • Total % Impedance up to Main LT Panel= 6.662 % Ώ. (Calculated as per (B))
  • CALCULATE % RESISTANCE & REACTANCE OF CABLE-1 (300 SQ.MM)
  • % Resistance of Cable =Base KVA (TC Capacity) x Cable Resistance x Length of Cable / (System Voltage in KV)²x10.
  • % Resistance of Cable =1000 x 0.129 x 1 x 80 / 0.415 x 0.415 x10
  • % Resistance of Cable =5.99 % Ώ
  • % Reactance of Cable =Base KVA (TC Capacity) x Cable Reactance x No of Run x Length of Cable / (System Voltage in KV)² x10.
  • % Reactance of Cable =1000 x 0.071 x 1 x 80 / 0.415×0.415×10
  • % Reactance of Cable =3.27 % Ώ
  • % Impedance of Cable =√ R² + X²
  • % Impedance of Cable =√ (5.99) ² + (3.27) ²
  • % Impedance of Cable =6.82 % Ώ.
  • Total % Impedance up to Sub Panel-1 = % Impedance up Main LT Panel  +%Cable Impedance
  • Total % Impedance = 5.92+6.82 % Ώ.
  • Total % Impedance = 13.49% Ώ.
  • Fault KVA on Sub Panel-1= Base MVA x100 / Total % Impedance.
  • Fault KVA on Sub Panel-1 = 1 x100 / 13.49.
  • Fault KVA on Sub Panel-1 = 7.41 KVA.
  • Short Circuit Current at Sub Panel-1 = Fault KVA on Sub Panel-1 / 1.732 x System Voltage at Fault Point.
  • Short Circuit Current at Sub Panel-1 = 7.41 / 1.732 x0.415.
  • Short Circuit Current at Sub Panel-1 = 10.33 KA.
  • Short Circuit Current at Sub Panel-1 = 11 KA

(5) SHORT CIRCUIT CURRENT AT SUB PANEL-2:

  • To calculate Short Circuit Current at Sub Panel-2, We need to sum Total Impedance of the system up to Sub Panel-2 (Total Impedance up to Main LT Panel + Impedance of LT Cable-2).
  • Total % Impedance up to Main LT Panel= 6.662 % Ώ. (Calculated as per (B))
  • CALCULATE % RESISTANCE & REACTANCE OF CABLE-2 (95 SQ.MM)
  • % Resistance of Cable =Base KVA (TC Capacity) x Cable Resistance x Length of Cable / (System Voltage in KV)²x10.
  • % Resistance of Cable =1000 x 0.409 x 1 x 80 / 0.415 x 0.415×10
  • % Resistance of Cable =19 % Ώ
  • % Reactance of Cable =Base KVA (TC Capacity) x Cable Reactance x No of Run x Length of Cable / (System Voltage in KV)² x10.
  • % Reactance of Cable =1000 x 0.072 x 1 x 80 / 0.415×0.415×10
  • % Reactance of Cable =3.36 % Ώ
  • % Impedance of Cable =√ R² + X²
  • % Impedance of Cable =√ (19) ² + (3.36) ²
  • % Impedance of Cable =19.294 % Ώ.
  • Total % Impedance up to Sub Panel-2 = % Impedance up Main LT Panel +%Cable Impedance
  • Total % Impedance up to Sub Panel-2 = 6.662+19.294 % Ώ.
  • Total % Impedance up to Sub Panel-2 = 25.956% Ώ.
  • Fault KVA on Sub Panel-2 = Base MVA x100 / Total % Impedance up to Sub Panel-2.
  • Fault KVA on Sub Panel-2 = 1 x100 / 25.956.
  • Fault KVA on Sub Panel-2 = 3.85 KVA.
  • Short Circuit Current at Sub Panel-2 = Fault KVA on Sub Panel-2 / 1.732 x System Voltage at Fault Point.
  • Short Circuit Current at Sub Panel = 3.85 / 1.732 x 415.
  • Short Circuit Current at Sub Panel = 5.36 KA.
  • Short Circuit Current at Sub Panel-2 = 6 KA

 CONCLUSION:

  • Shor Circuit Current at 11KV System = 18.37 KA.
  • Short Circuit Current at Transformer LT Side= 25.32 KA
  • Short Circuit Current at Main LT Panel = 21 KA
  • Short Circuit Current at Sub Panel-1 = 11 KA
  • Short Circuit Current at Sub Panel-2 = 6 KA