Heat Generated by Generator:

  • For generator set installations, the heat radiated by the generator can be estimated by
  • H (kW) =P X ((1/Eff)-1)
  • H (Btu/min) =P X ((1/EFF)-1) x56.9
  • Where:
  • H = Heat Radiated by the Generator (kW), (Btu/min)
  • P = Generator Output at Maximum Engine Rating (kW)
  • Eff = Generator Efficiency % / 100%
  • Example: 975 kW standby generator set has a generator efficiency of 92%. The generator radiant heat for this genset can be calculated as follows.
  • P = 975 kW
  • Efficiency = 92% = 0.92
  • H = 975 x ((1/92%) – 1)
  • H= 84.78 kW
  • H = 975 x ((1/92%) – 1) x 56.9
  • H = 4824 Btu/min

 Types of Ventilation System:

  • Type:1 (Preferred Design) (Routing Factor of 1)
  • Outside air is brought into the engine room through a system of ducts. These ducts should be routed between engines, at floor level, and discharge air near the bottom of the engine and generator. .
  • Ventilation air exhaust fans should be mounted or ducted at the highest point in the engine room. They should be directly over heat sources. This system provides the best ventilation with the least amount of air required.
  • Type 2 (Skid Design) (Routing Factor of 1)
  • Outside air into the engine room through a system of ducts and routes it between engines.
  • Type 2, however, directs airflow under the engine and generator so the air is discharged upward at the engines
  • The most economical method to achieve this design is to use a service platform. The platform is built up around the engines and serves as the top of the duct
  • Ventilation air exhaust fans should be mounted or ducted at the highest point in the engine room. They should be directly over heat sources.
  • This system provides the best ventilation with the least amount of air required.
  • Type 3 (Alternate Design) (Routing Factor of 1.5)
  • If Ventilation Type 1or Type 2 is not feasible, an alternative is Type 3; however, this routing configuration will require approximately 50% more airflow than Type 1.
  • Outside air is brought into the engine room utilizing fans or large intake ducts. The inlet is placed as far away as practical from heat sources and discharged into the engine room as low as possible. The air them flows across the engine room
  • Ventilation air exhaust fans should be mounted or ducted at the highest point in the engine room. Preferably, they should be directly over heat sources
  • Type 4 (Less Effective Design) (Routing Factor of 2.5)
  • If Ventilation Type 1, Type 2 and Type 3 are not feasible, then Type-4 method can be used; however, it provides the least efficient ventilation and requires approximately two and a half times the airflow of Ventilation Type 1
  • Outside air is brought into the engine room using supply fans, and discharged toward the turbocharger air inlets on the engines.
  • Ventilation exhaust fans should be mounted or duct from the corners of the engine room
  • This system mixes the hottest air in the engine room with the incoming cool air, raising the temperature of all air in the engine room.
  • It also interferes with the natural convection flow of hot air rising to exhaust fans.
  • Engine rooms can be ventilated this way, but it requires extra large capacity ventilating fans.

Ventilation for Generator:

  •  When Generator set installations in Room proper ventilation is required for Generator set.
  • A properly designed engine room ventilation system will maintain engine room air temperatures within 8.5 to 12.5°C (15 to 22.5°F) above the ambient air temperature.
  • For example, If the engine room temperature is 24°C (75°F) without the engine running, the ventilation system should maintain the room temperature between 32.5°C (90°F) and 36.5°C (97.5°F) while the engine is in operation.
  • Ensures engine room temperature does not exceed 49°C (120°F).
  • Required Ventilating Air is calculated as
  • V=((H / D x Cp x T)+ Combustion Air) X F
  • Where:
  • V = Ventilating Air (m3/min), (cfm)
  • H = Heat Radiation i.e. engine, generator, aux (kW),(Btu/min)
  • D = Density of Air at air temperature 38°C (100°F). The density is 1.099 kg/m3 (0.071 lb/ft3)
  • CP = Specific Heat of Air (0.017 kW x min/kg x °C),(0.24 Btu/LBS/°F)
  • T = Permissible temperature rise in engine room (°C), (°F)
  • F = Routing factor based on the ventilation type
  • Example: The engine room for generator set has a Type 1 ventilation routing configuration and a dedicated duct for combustion air. It has a heat rejection value of 659 kW (37,478 Btu/min) and a permissible rise in engine room temperature of 11°C (20°F).
  • V=((659 / 1.0099X0.017X11)+ 0)X1
  • V = 3206.61 m3/min
  • V=((659 / 0.071 X 0.024 X 20)+ 0)X1
  • V = 109970.7 cfm

About Jignesh.Parmar
Jignesh Parmar has completed M.Tech (Power System Control), B.E(Electrical). He is member of Institution of Engineers (MIE) and CEng,India. Membership No:M-1473586.He has more than 16 years experience in Transmission -Distribution-Electrical Energy theft detection-Electrical Maintenance-Electrical Projects (Planning-Designing-Technical Review-coordination -Execution). He is Presently associate with one of the leading business group as a Deputy Manager at Ahmedabad,India. He has published numbers of Technical Articles in “Electrical Mirror”, “Electrical India”, “Lighting India”,”Smart Energy”, “Industrial Electrix”(Australian Power Publications) Magazines. He is Freelancer Programmer of Advance Excel and design useful Excel base Electrical Programs as per IS, NEC, IEC,IEEE codes. He is Technical Blogger and Familiar with English, Hindi, Gujarati, French languages. He wants to Share his experience & Knowledge and help technical enthusiasts to find suitable solutions and updating themselves on various Engineering Topics.

12 Responses to Calculate Required Air ventilation and Heat generation of D.G Set

  1. Sarphraz Pathan says:

    Dear sir Do you have documents about protection or power systems?  Sent from Yahoo Mail on Android

  2. Vivekanand Pandey says:

    Thanks sir for giving me valuable notes

  3. Zahid Ali says:

    Excellent and surperb working

    On 1 Jan 2018 20:11, “Electrical Notes & Articles” wrote:

    > Jignesh.Parmar posted: “Heat Generated by Generator: For generator set > installations, the heat radiated by the generator can be estimated by H > (kW) =P X ((1/Eff)-1) H (Btu/min) =P X ((1/EFF)-1) x56.9 Where: H = Heat > Radiated by the Generator (kW), (Btu/min) P = Generator ” >

  4. Hailemaryam Tilahun says:

    First of all i would like to say Happy new year 2018 and thank you very much for your email attachment God bless you!!!

  5. SAN Sereyvathna says:

    Hello,

    Could you kindly upload calculation file again? As you previous link was broken.

    Thank you.

  6. Amith says:

    Dear Sir,
    Can you please provide lecture notes on confined space ventilation. How much amount of forced ventilation required in tanks, pipe lines and other confined spaces. Specially for maritime industry.

    Amit.

  7. Surya Mani says:

    To Dear sir I have no job so. Your combination very poor For contacting Je Electrical Eng. Surya Mani 8800424830

    On 01-Jan-2018 8:43 PM, “Electrical Notes & Articles” wrote:

    > Jignesh.Parmar posted: “Heat Generated by Generator: For generator set > installations, the heat radiated by the generator can be estimated by H > (kW) =P X ((1/Eff)-1) H (Btu/min) =P X ((1/EFF)-1) x56.9 Where: H = Heat > Radiated by the Generator (kW), (Btu/min) P = Generator ” >

  8. Angelito Cortez says:

    Thanks A Lot.

  9. Manmohan Prajapati says:

    Sir mujhe power plant se related samjna he please gide sir

  10. Abhimanyu singh says:

    Dear sir,plz tell me what is the importance of transformer having vector group DD0yn11, for same secondary 690 v output why star and delta both is necessary.

  11. Rakesh S says:

    HI.. Could you please clarify whats ‘combustion air’ in the formula.. Its been taken as zero in your ..Thanks in advance..

  12. Rakesh S says:

    HI .sry ..I didn’t notice you’ve considered type1…Thanks senor…

Leave a Reply

Fill in your details below or click an icon to log in:

WordPress.com Logo

You are commenting using your WordPress.com account. Log Out /  Change )

Google+ photo

You are commenting using your Google+ account. Log Out /  Change )

Twitter picture

You are commenting using your Twitter account. Log Out /  Change )

Facebook photo

You are commenting using your Facebook account. Log Out /  Change )

Connecting to %s

%d bloggers like this: