Over Current Relay(Type-Application-Connection):

Types of protection:

  • Protection schemes can be divided into two major groupings:
  1. Unit schemes
  2. Non-unit schemes

1) Unit Type Protection

  • Unit type schemes protect a specific area of the system, i.e., a transformer, transmission line, generator or bus bar.
  • The unit protection schemes is based on Kerchief’s current law – the sum of the currents entering an area of the system must be zero. Any deviation from this must indicate an abnormal current path. In these schemes, the effects of any disturbance or operating condition outside the area of interest are totally ignored and the protection must be designed to be stable above the maximum possible fault current that could flow through the protected area.

2) Non unit type protection

  • The non-unit schemes, while also intended to protect specific areas, have no fixed boundaries. As well as protecting their own designated areas, the protective zones can overlap into other areas. While this can be very beneficial for backup purposes, there can be a tendency for too great an area to be isolated if a fault is detected by different non unit schemes.
  •  The most simple of these schemes measures current and incorporates an inverse time characteristic into the protection operation to allow protection nearer to the fault to operate first.
  • The non unit type protection system includes following schemes:
  • (A)  Time graded over current protection
  • (B)  Current graded over current protection
  • (C) Distance or Impedance Protection

(A) Over current protection

  • This is the simplest of the ways to protect a line and therefore widely used.
  • It owes its application from the fact that in the event of fault the current would increase to a value several times greater than maximum load current.
  • It has a limitation that it can be applied only to simple and non costly equipments.

(B) Earth fault protection

  • The general practice is to employ a set of two or three over current relays and a separate over current relay for single line to ground fault. Separate earth fault relay provided makes earth fault protection faster and more sensitive.
  • Earth fault current is always less than phase fault current in magnitude. Therefore, relay connected for earth fault protection is different from those for phase to phase fault protection.

 Various types of Line Faults:

No Type of Fault Operation of  Relay
1 Phase to Ground fault (Earth Fault) Earth Fault Relay
2 Phase to Phase fault Not with Ground Related Phase Over current relays
3 Double phase to Ground fault Related Phase Over current relays and Earth Fault relays

 Over current Relay:

  • A relay that operates or picks up when it’s current exceeds a predetermined value (setting value) is called Over Current Relay.
  • Over current protection protects electrical power systems against excessive currents which are caused by short circuits, ground faults, etc. Over current relays can be used to protect practically any power system elements, i.e. transmission lines, transformers, generators, or motors.
  • For feeder protection, there would be more than one over current relay to protect different sections of the feeder. These over current relays need to coordinate with each other such that the relay nearest fault operates first. Use time, current and a combination of both time and current are three ways to discriminate adjacent over current relays.

 Over Current Relay gives Protection against:

  1. Over current includes short-circuit protection.
  2. Short circuits can be
  3. Phase faults
  4. Earth faults
  5. Winding faults
  • Short-circuit currents are generally several times (5 to 20) full load current. Hence fast fault clearance is always desirable on short circuits.

 Primary Requirement of Over Current Protection:

  • The protection should not operate for starting currents, permissible over current, current surges. To achieve this, the time delay is provided (in case of inverse relays).
  • The protection should be co-ordinate with neighboring over current protection.
  • Over current relay is a basic element of over current protection.

 Purpose of over current Protection

  • Detect abnormal conditions
  • Isolate faulty part of the system
  • Speed Fast operation to minimize damage and danger
  • Discrimination Isolate only the faulty section
  • Dependability / reliability
  • Security / stability
  • Cost of protection / against cost of potential hazards

Over Current Relay Ratings:

  • In order for an over current protective device to operate properly, over current protective device ratings must be properly selected. These ratings include voltage, ampere and interrupting rating.
  • If the interrupting rating is not properly. Selected, a serious hazard for equipment and personnel will exist. Current limiting can be considered as another over current protective device rating, although not all over current protective devices are required to have this characteristic
  • Voltage Rating: The voltage rating of the over current protective device must be at least equal to or greater than the circuit voltage. The over current protective device rating can be higher than the system voltage but never lower.
  • Ampere Rating: The ampere rating of a over current protecting device normally should not exceed the current carrying capacity of the conductors As a general rule, the ampere rating of a over current protecting device is  selected at 125% of the continuous load current

 Difference Between Over current Protection & Over Load Protection:

  • Over current protection protects against excessive currents or currents beyond the acceptable current ratings, which are resulting from short circuits, ground faults and overload conditions.
  • While, the overload protection protects against the situation where overload current causes overheating of the protected equipment.
  • The over current protection is a bigger concept So that the overload protection can be considered as a subset of over current protection.
  • The over current relay can be used as overload (thermal) protection when protects the resistive loads, etc., however, for motor loads, the over current relay cannot serve as overload protection Overload relays usually have a longer time setting than the over current relays.

  Type of Over Current Relay:

  • (A)  Instantaneous Over Current (Define Current) Relay
  • (B)  Define Time Over Current Relay
  • (C) Inverse Time Over Current Relay (IDMT Relay)
  • Moderately Inverse
  • Very Inverse Time
  • Extremely Inverse
  • (D) Directional over Current Relay.

 (A) Instantaneous Over Current Relay (Define Current):

  • Definite current relay operate instantaneously when the current reaches a predetermined value.
  • Operates in a definite time when current exceeds its Pick-up value.
  • Its operation criterion is only current magnitude (without time delay).
  • Operating time is constant.
  • There is no intentional time delay.


  • Coordination of definite-current relays is based on the fact that the fault current varies with the position of the fault because of the difference in the impedance between the fault and the source
  • The relay located furthest from the source operate for a low current value
  • The operating currents are progressively increased for the other relays when moving towards the source.
  • It operates in 0.1s or less
  • Application: This type is applied to the outgoing feeders

(B) Definite Time Over current Relays:

  • In this type, two conditions must be satisfied for operation (tripping), current must exceed the setting value and the fault must be continuous at least a time equal to time setting of the relay. Modern relays may contain more than one stage of protection each stage includes each own current and time setting.


  • For Operation of Definite Time Over Current Relay operating time is constant
  • Its operation is independent of the magnitude of current above the pick-up value.
  • It has pick-up and time dial settings, desired time delay can be set with the help of an intentional time delay mechanism.
  • Easy to coordinate.
  • Constant tripping time independent of in feed variation and fault location.

Drawback of Relay:

  • The continuity in the supply cannot be maintained at the load end in the event of fault.
  • Time lag is provided which is not desirable in on short circuits.
  • It is difficult to co-ordinate and requires changes with the addition of load.
  • It is not suitable for long distance transmission lines where rapid fault clearance is necessary for stability.
  • Relay have difficulties in distinguishing between Fault currents at one point or another when fault impedances between these points are small, thus poor discrimination.

Application: Definite time over current relay is used as:

  • Back up protection of distance relay of transmission line with time delay.
  • Back up protection to differential relay of power transformer with time delay.
  • Main protection to outgoing feeders and bus couplers with adjustable time delay setting.

(C) Inverse Time Over current Relays (IDMT Relay):

  • In this type of relays, operating time is inversely changed with current. So, high current will operate over current relay faster than lower ones. There are standard inverse, very inverse and extremely inverse types.
  • Discrimination by both ‘Time’ and ‘Current’. The relay operation time is inversely proportional to the fault current.
  • Inverse Time relays are also referred to as Inverse Definite Minimum Time (IDMT) relay


  • The operating time of an over current relay can be moved up (made slower) by adjusting the ‘time dial setting’. The lowest time dial setting (fastest operating time) is generally 0.5 and the slowest is 10.
  • Operates when current exceeds its pick-up value.
  • Operating time depends on the magnitude of current.
  • It gives inverse time current characteristics at lower values of fault current and definite time characteristics at higher values
  • An inverse characteristic is obtained if the value of plug setting multiplier is below 10, for values between 10 and 20 characteristics tend towards definite time characteristics.
  • Widely used for the protection of distribution lines.
  • Based on the inverseness it has three different types. 4

(1)  Normal Inverse Time Over current Relay:

  • The accuracy of the operating time may range from 5 to 7.5% of the nominal operating time as specified in the relevant norms.
  • The uncertainty of the operating time and the necessary operating time may require a grading margin of 0.4 to 0.5 seconds.
  • used when Fault Current is dependent on generation of Fault  not fault location
  • Relatively small change in time per unit of change of current.


  • Most frequently used in utility and industrial circuits. especially applicable where the fault magnitude is mainly dependent on the system generating capacity at the time of fault

(2)  Very Inverse Time Over current Relay:

  • Gives more inverse characteristics than that of IDMT.
  • Used where there is a reduction in fault current, as the distance from source increases.
  • Particularly effective with ground faults because of their steep characteristics.
  • Suitable if there is a substantial reduction of fault current as the fault distance from the power source increases.
  • Very inverse over current relays are particularly suitable if the short-circuit current drops rapidly with the distance from the substation.
  • The grading margin may be reduced to a value in the range from 0.3 to 0.4 seconds when over current relays with very inverse characteristics are used.
  • Used when Fault Current is dependent on fault location.
  • Used when Fault Current independent of normal changes in generating capacity.

(3)  Extremely Inverse Time Over current Relay:

  • It has more inverse characteristics than that of IDMT and very inverse over current relay.
  • Suitable for the protection of machines against overheating.
  • The operating time of a time over current relay with an extremely inverse time-current characteristic is approximately inversely proportional to the square of the current
  • The use of extremely inverse over current relays makes it possible to use a short time delay in spite of high switching-in currents.
  • Used when Fault current is dependent on fault location
  • Used when Fault current independent of normal changes in generating capacity.


  • Suitable for protection of distribution feeders with peak currents on switching in (refrigerators, pumps, water heaters and so on).
  • Particular suitable for grading and coordinates with fuses and re closes
  • For the protection of alternators, transformers. Expensive cables, etc.

 (4)  Long Time Inverse over current Relay:

  • The main application of long time over current relays is as backup earth fault protection.

 (D) Directional Over current Relays

  • When the power system is not radial (source on one side of the line), an over current relay may not be able to provide adequate protection. This type of relay operates in on direction of current flow and blocks in the opposite direction.
  • Three conditions must be satisfied for its operation: current magnitude, time delay and directionality. The directionality of current flow can be identified using voltage as a reference of direction.

 Application of Over Current Relay:

  • Motor Protection:
  • Used against overloads and short-circuits in stator windings of motor.
  • Inverse time and instantaneous over current phase and ground
  • Over current relays used for motors above 1000kW.
  • Transformer Protection:
  • used only when the cost of over current relays are not justified
  • Extensively also at power-transformer locations for external-fault back-up protection.
  • Line Protection:
  • On some sub transmission lines where the cost of distance relaying cannot be justified.
  • primary ground-fault protection on most transmission lines where distance relays are used for phase faults
  • For ground back-up protection on most lines having pilot relaying for primary protection.
  • Distribution Protection:
  • Over Current relaying is very well suited to distribution system protection for the following reasons:
  • It is basically simple and inexpensive
  • Very often the relays do not need to be directional and hence no PT supply is required.
  • It is possible to use a set of two O/C relays for protection against inter-phase faults and a separate Over Current relay for ground faults.

 Connection of over current and Earth Fault Relay:

(1)  3 Nos O/C Relay for Over Current and Earth Fault Protection:

  • For 3-phase faults the over current relays in all the 3-phases act.
  • For phase to phase faults the relays in only the affected phases operate.
  • For single line to ground faults only the relay in the faulty phase gets the fault current and operates.
  • Even then with 3 Over current Relay, the sensitivity desired and obtainable with earth leakage over current relays cannot be obtained in as much as the high current setting will have to be necessarily adopted for the Over current Relay to avoid operation under maximum load condition.


  • Over current relays generally have 50% to 200% setting while earth leakages over current relays have either 10% to 40% or 20% to 80% current settings.
  • One important thing to be noted here is that the connection of the star points of both the C.T. secondary’s and relay windings by a neutral conductor should be made.
  •  A scheme without the neutral conductor will be unable to ensure reliable relay operation in the event of single phase to earth faults because the secondary current in this case (without star-point interconnection) completes its circuit through relay and C.T. windings which present large impedance. This may lead to failure of protection and sharp decrease in reduction of secondary currents by CTs.
  •  It is not sufficient if the neutral of the CTs and neutral of the relays are separately earthed. A conductor should be run as stated earlier.

 (2)  3 No O/C Relay+ 1 No E/F Relay for Over Current and Earth Fault Protection:

  • The scheme of connection for 3 Nos Over current Relay 1 No Earth Fault Relay is shown in figure.


  • Under normal operating conditions and three phase fault conditions the current in the 3-phase are equal and symmetrically displaced by 12 Deg. Hence the sum of these three currents is zero. No current flow through the earth fault relay.
  • In case of phase to phase faults (say a short between R and Y phases) the current flows from R-phase up to the point of fault and return back through ‘Y’ phase. Thus only O/L relays in R and Y phases get the fault and operate.
  • Only earth faults cause currents to flow through E/L relay. A note of caution is necessary here. Only either C.T secondary star point of relay winding star point should be earthed.
  • Earthing of both will short circuit the E/L relay and make it inoperative for faults.

 (3)  2 No O/C Relay + 1 No E/F Relay for Over Current and Earth Fault Protection:

  • The two over current relays in R&B phases will respond to phase faults. At least one relay will operate for fault involving two phase.


  •  For fault involving ground reliance is placed on earth fault relay.
  • This is an economical version of 3-O/L and 1-E/L type of protection as one overcurrent relay is saved. With the protection scheme as shown in Figure complete protection against phase and ground fault is afforded

 Current Transformer Secondary Connections:

  • For protection of various equipment of Extra High Voltage class, the Star point on secondary’s of CT should be made as follows for ensuring correct directional sensitivity of the protection scheme
  • Transmission Line , Bus Bar & Transformer:
  • For Transmission Lines – Line side
  • For Transformers – Transformer side
  • For Bus bar – Bus side 8
  • Generator Protection:
  • Generator Protection – Generator Side
  • 9The above method has to be followed irrespective of polarity of CT’s on primary side.
  • For example, in line protection, if ‘P1’ is towards bus then ‘S2’s are to be shorted and if ‘ P2’ is towards bus then ‘S1’s are to be shorted.

 Standard over Current & Earth Fault Protection:


Name of the Equipment



11 KV Feeders

(A) 2 No Over Current and one no Earth Fault IDMT relays
(B) 2 No Instantaneous Over current (highest) and one no Instantaneous Earth fault relay


8 MVA Capacity  OR Two Transformer in a Sub Station ( Irrespective of Capacity)


HV side : 33 KV Breaker ( Individual or Group Control with 3 Over Current and One Earth Fault IDMT relaysLV Side: Individual 11 KV Breakers with 3 Over Current and One Earth Fault IDMT relays


8 MVA Power Transformer

Differential relays OR REF relays on LV side


Only one PTR in a Sub Station (Less than 8 MVA)

HV Side : HG fuseLV Side : 11 KV Breaker with 3 Over Current and one  E/F IDMT relay


About Jignesh.Parmar
Jignesh Parmar has completed M.Tech (Power System Control), B.E(Electrical) from Gujarat University. He has more than 13 years experience in Power Transmission-Power Distribution-Electrical energy theft detection-Electrical Maintenance-Electrical Projects(Planning-Designing-coordination-Execution). He is Presently associate with one of the leading business group as a Deputy Manager at Ahmedabad,India. He is Freelancer Programmer of Advance Excel and design useful Excel Sheets of Electrical Engineering as per IS,NEC,IEC,IEEE codes. He is technical Author for "Electrical Mirror" and "Electrical India" Magazines. He is Technical Blogger and Familiar with English, Hindi, Gujarati, French languages. He wants to Share his experience & knowledge and help technical enthusiasts to find suitable solutions and updating themselves on various Engineering Topics.

34 Responses to Over Current Relay(Type-Application-Connection):

  1. Hemrajsinh D. Chudasama says:

    Very good present of the new year 2013.Thanks Jigneshbhai.

    Hemrajsinh Chudasama

  2. J sridharan says:

    Dear Jignesh Parmar

    Thanks sir

    The information you are sharing is very useful.

    Can you tell me regarding diff protection scheme for transformer, DG set



  3. rakesh verma says:

    Thanks sir,
    your information are very useful . i fight interview essely.

  4. sagar b n says:

    Thanks sir
    The concept is very easy to understand.
    can i get information about voltage control through reactive power control

    • The main aim of controlling reactive power is improve Power Quality,Losses of System but by doing this we indirectly control voltage up to certain level.Main Method of controlling voltage is to control Voltage drop or % Voltage Regulation of System. We can not make vast variation on Voltage by controlling Reactive Energy.
      I will upload Note of How to control Reactive Power-size and Location of Capacitor in System in next month…

      • partha sarothi sikder says:

        your blog is really god and very useful thank u sir ..keep uploading.take care

  5. deepak goswami says:

    Dear jigneshbhai,
    It is a good information but i would like to say about how about the types of fiiting used in small area /commercial any fixed prospective view that i may be considered & what types of d.b/elect. panel / apfcr panel / hvac panel / plumbing panel / fire fighting panel / uss / x-mer / vcb / that my question is arise what type of any similar project or area base statement can be find out this generallly caculation of electrical project would be done. Can this guide for me.

    Thanks & regards

  6. jitesh says:


  7. namita says:

    hi jignesh,
    your articles are really usefull and easy to understand.
    refering to above article, could u pl help me on coordination between instantaneous (50) and IDMT (51) characteristics of overcurrent relay?

  8. yogesh murthy n says:

    sir your information on relay is very useful so please provide me information on high voltage distribution systems.
    yogesh murthy.n from mysore

  9. Mahseh Mathpati says:

    the information is very useful i will read and come back, thanks for sharing.
    Mahesh Mathpati from raichur

  10. Swetha says:

    Thank u Sir, This information related to relays is very detailed and it helped me in completing my project work. Please be posting much more information related to latest technological devices and i would be very eager to read all ur posts

  11. hello sir i am vijay prasan kumar . i am working as a electrical engineer in uae . i need relay cordination concept if u have means can u send the mail vijayprasankkumar@gmail.com

  12. Vinod says:

    Mr. Jignesh
    I am Vinod Shimpi working as Asistant Engineer (Testing) MSEDCL, Maharashtra ,. Thank you very very much for your valuable and noble help / service to all electrical engineers It’s a very collective information very useful to any Electrical Engineer.
    Once again Thanks for your efforts and sharing the knowledge to everybody…
    Very Nice job and keep it up…………..
    Thanks & Regards
    Vinod Shimpi

  13. kishore says:

    jignesh sir

    i want to know the maximum operation time of over current relay used in distribution system like 1sec or 2sec

  14. kishore says:

    hi sir
    what is the purpose of single throw switch exactly, where it is used in in underground cables or overhead lines,
    can we use any protective device like overcurrent relay in series with the single throw switch what it indicates….
    sir plesase give me reply…….

  15. Aakash Shah says:

    hi sir,
    ur article is very useful for me to find out my answers thank u very much sir

  16. mubarak says:

    how to set the MRMU 13.8 kv Rely? rely setting we dightle rely

  17. saidireddy says:

    Hai Sir i’ am working in cement industry relays is tha important subject and important in plant thanks Sir

  18. s.anandkumar says:

    Good information.

  19. ashok says:

    it’s great job to share our knowledge with us

    • khan says:

      Hi sir, i am requesting for the software of breaker and cable short circuit calculation.

      please sir,,,,,, waiting for your kind response…………

  20. om jha says:

    HI SIR

  21. Dipak says:

    Please tell me i have 10 hp water pump and i went to protect from over current and earth fault and short circuit protection so can i use over current relay with only one ct connected in any one phase or mpcb (motor protector circuit breaker ) and what is different between over current relay and mpcb .


    Dear Mr. Jignesh,
    Good Morning,
    Your explanation and the drawings are quite useful for the young engineers & developing Electrical personnel’s.
    All the very best.
    Thanks & Regards,
    Sasikumar Devabalan
    Electrical Supervisor,

  23. yousef says:

    HI .dear
    how to calculate and set the over current protection time daley and instantanous. I need a real example and what doesnt mean tap , tms .

  24. yousef says:

    please help me

  25. yousef says:

    Dear Mr. Jignesh

    Good Morning,

    I need information about transformer protection becauce i want to make project about it

  26. yousef says:

    pls help me and sended to me as soon as you

  27. yousef1970 says:

    dear sir

    pls help me to send me how to calculate over current relay by inverse time for fualt happen in transformer

  28. johny says:

    Can you please help me to understand directional over current relays,particularly how to define direction using MTA?

  29. viswa says:

    Hi sir i am working in alstom projects by pothigai power soluion i saw your articles it is very useful to all eees so all student get some knowledge

Leave a Reply

Fill in your details below or click an icon to log in:

WordPress.com Logo

You are commenting using your WordPress.com account. Log Out / Change )

Twitter picture

You are commenting using your Twitter account. Log Out / Change )

Facebook photo

You are commenting using your Facebook account. Log Out / Change )

Google+ photo

You are commenting using your Google+ account. Log Out / Change )

Connecting to %s

%d bloggers like this: