IS 1678/IS 1445
IS: 1678-1960
16. PCC Pole
- Class of Pole=Class1 Length of Pole=17 meter , Min Ultimate Transverse Load=3000kg
- Class of Pole=Class2 Length of Pole=17 meter , Min Ultimate Transverse Load=2300kg
- Class of Pole=Class3 Length of Pole=17 meter , Min Ultimate Transverse Load=1800kg
- Class of Pole=Class4 Length of Pole=17 meter , Min Ultimate Transverse Load=1400kg
- Class of Pole=Class5 Length of Pole=16 meter , Min Ultimate Transverse Load=1100kg
- Class of Pole=Class6 Length of Pole=12.5 meter , Min Ultimate Transverse Load=1000kg
- Class of Pole=Class7 Length of Pole=12 meter , Min Ultimate Transverse Load=800kg
- Class of Pole=Class8 Length of Pole=12 meter , Min Ultimate Transverse Load=700kg
- Class of Pole=Class9 Length of Pole=11 meter , Min Ultimate Transverse Load=450kg
- Class of Pole=Class10 Length of Pole=09 meter , Min Ultimate Transverse Load=300kg
- Class of Pole=Class11 Length of Pole=7.5 meter , Min Ultimate Transverse Load=200kg
17. PCC Pole Tolerance
- Tolerance: The tolerance of overall length of the poles shall be + 15 mm. The tolerance on cross-sectional dimensions shall be + 3 mm. The tolerance on cross-sectional dimensions shall be + 3 mm. The tolerance on uprightness of the pole shall be 0.5 per cent
18. PCC Pole depth in Ground
- Length of Pole= 6m To 7.5 m Min depth in ground= 1.2m
- Length of Pole= 8m To 9.0 m Min depth in ground= 1.5m
- Length of Pole= 9.5m To 11 m Min depth in ground= 1.8m
- Length of Pole= 11.5m To 13 m Min depth in ground= 2.0m
- Length of Pole= 13.5m To 14.5 m Min depth in ground= 2.2m
- Length of Pole= 15m To 16.5 m Min depth in ground= 2.3m
- Length of Pole= 17m Min depth in ground= 2.4m
IS: 1445-1966
19. Porcelain Insulator
- Overhead line insulators are divided into two types according to their construction.
- Type A- An insulator unit in which the length of the shortest puncture patch through solid insulating material is at least equal to half the length of the shortest flashover path through air outside the insulator.
- Type B- An insulator or an insulator unit in which the length of the shortest puncture patch through solid insulating material is less than half the length of the shortest flash over path through air outside the insulator