Calculation of IDMT Over current & Earth Fault Relay Setting:

 IDMT Over current & Earth Fault Relay Setting:

  • Calculate IDMT Over Current Relay Setting (50/51)
  • Calculate IDMT Over Current Relay Pick up setting.
  • Calculate IDMT Over Current Relay PSM.
  • Calculate IDMT Over Current Relay Time setting.
  • Calculate Actual Operating time according to Various IES Curve.
  • Calculate Low current Setting(I>).
  • Calculate High Current Setting(I>>)
  • Calculate Actual Operating Time of Relay(t>)
  • Calculate Actual Operating Time of Relay(t>>)
  • Calculate IDMT Earth Fault Relay Setting (50N/51N) 
  •  Calculate IDMT Earth Fault Relay Pick up setting.
  • Calculate IDMT Earth Fault Relay PSM
  • Calculate IDMT Earth Fault Relay Time setting
  • Calculate Actual Operating time according to Various IES Curve.
  • Calculate Low current Setting(Ie>)
  • Calculate High Current Setting(Ie>>)
  •  Calculate Actual Operating Time of Relay(te>)
  •  Calculate Actual Operating Time of Relay(te>>)

Free Download     Buy UNLOCK Sheet

About these ads

About Jignesh.Parmar
Jignesh Parmar has completed his B.E(Electrical) from Gujarat University. He has more than 11 years experience in Power Transmission-Power Distribution-Electrical energy theft detection-Electrical Maintenance-Electrical Projects(Planning-Designing-coordination-Execution). He is Presently associate with one of the leading business group as a Assistant Manager at Ahmedabad,India. He is Freelancer Programmer of Advance Excel and design useful Excel Sheets of Electrical Engineering as per IS,NEC,IEC,IEEE codes. He is technical Author for "Electrical Mirror" and "Electrical India" Magazines. He is Technical Blogger and Familiar with English, Hindi, Gujarati, French languages. He wants to Share his experience & knowledge and help technical enthusiasts to find suitable solutions and updating themselves on various Engineering Topics.

17 Responses to Calculation of IDMT Over current & Earth Fault Relay Setting:

  1. SAJOSH JACOB GEORGE says:

    Could u please explain selection of MCB, ELCB and cable selection for Electrical DBs?
    light, power, AC unit, single phase,three phase etc..

    • Refer Page of “Electrical Tools” of this Blog……….

      • ALI says:

        What is the settings of protection relay Micom p121 connected to 208 feeder incomer circuit breaker CT 1600/5 Transformer 2300/208v z= 6.03% 500kva. 2300v feeder supplied via oil fuse switch with 160 amps fuses. Please find me O/C & EF 208 v incomer relay settings?

  2. Sanjay Limbore says:

    In case of 22kv ht line, if loose or improper connection at any phase , it always show fault at LT side for Earth fault and LT breaker keeps on tripping . Observed this condition mostly when rainy seasons starts.

  3. blesson says:

    Hi Jignesh,

    You have a real good workmanship ..Aprreciate the efforts and accuracy.

    Do you have a excel sheet to do touch volatage calculation for a site.

    Also how to calculate the impedances on phase sub circuits , sub circuits earth , submains and phase..please assist me

  4. prathap says:

    hi jignesh thanks for ur wonderful work i av one request can u tel me that how to calculate impulse calculation for power transformers ,because this known only few people am also design power transformer design engineer am waiting for ur reply

  5. sami says:

    thank you very much for these useful programs

  6. Arul says:

    hello sir

    Your are awesome

    Ur dedication in Electrical field is impressive
    Thank you very much for the information on Electrical safety clearance

  7. Ashok Gupta says:

    Dear sir,
    Thanks for sharing the calculations. Can you please give me the setting calculations for 64R relay.

  8. Gaurav shah says:

    Dear sir

    we have motor of 200 kw , FLC 24 A Ht motor ABB make with we have used SPAM 140c MPR relay kindly tells us how relay setting is done.for example what value of current is set of I> I>> etc.

    Regards
    Gaurav shah

  9. hardip dodiya says:

    i just want to tell u you…sir..

    you make all sense of electrical parameter to us….working and guide like god of electrical engineering….thank you so much for your support.

  10. hardip dodiya says:

    Que.1 why TR NCT ratio higher than primary side CT? might be for fast response at small fault current? nt clear.

  11. hardip dodiya says:

    Que.1 In 220/66/11 switchyard 220kv level we use Y-Y1 type vector group trafo and 66kv side as general we know Dy11 used.

    pls answer sir…

  12. tonmoy says:

    thank u so much

  13. zakeer husssain says:

    Thanks alot

  14. achyut says:

    Gud afternoon Sir.
    For elect. Designing which course will be better- to develop and calculate

Leave a Reply

Fill in your details below or click an icon to log in:

WordPress.com Logo

You are commenting using your WordPress.com account. Log Out / Change )

Twitter picture

You are commenting using your Twitter account. Log Out / Change )

Facebook photo

You are commenting using your Facebook account. Log Out / Change )

Google+ photo

You are commenting using your Google+ account. Log Out / Change )

Connecting to %s

Follow

Get every new post delivered to your Inbox.

Join 3,956 other followers

%d bloggers like this: