MCB/MCCB/ELCB/RCCB
March 20, 2011 23 Comments
MCB/MCCB/ ELCB /RCBO/ RCCB:>>>>>>>>>> Donload Note in PDF
MCB (Miniature Circuit Breaker)
- Rated current not more than 100 A.
- Trip characteristics normally not adjustable.
- Thermal or thermal-magnetic operation.
MCCB (Moulded Case Circuit Breaker):
- Rated current up to 1000 A.
- Trip current may be adjustable.
- Thermal or thermal-magnetic operation.
Air Circuit Breaker:
- Rated current up to 10,000 A.
- Trip characteristics often fully adjustable including configurable trip thresholds and delays.
- Usually electronically controlled—some models are microprocessor controlled.
- Often used for main power distribution in large industrial plant, where the breakers are arranged in draw-out enclosures for ease of maintenance.
Vacuum Circuit Breaker:
- With rated current up to 3000 A,
- These breakers interrupt the arc in a vacuum bottle.
- These can also be applied at up to 35,000 V. Vacuum breakers tend to have longer life expectancies between overhaul than do air circuit breakers.
RCD (Residual Current Device) / RCCB( Residual Current Circuit Breaker) :
- Phase (line) and Neutral both wires connected through RCD.
- It trips the circuit when there is earth fault current.
- The amount of current flows through the phase (line) should return through neutral .
- It detects by RCD. any mismatch between two currents flowing through phase and neutral detect by RCD and trip the circuit within 30Miliseconed.
- If a house has an earth system connected to an earth rod and not the main incoming cable, then it must have all circuits protected by an RCD (because u mite not be able to get enough fault current to trip a MCB)
- The most widely used are 30 mA (milliamp) and 100 mA devices. A current flow of 30 mA (or 0.03 amps) is sufficiently small that it makes it very difficult to receive a dangerous shock. Even 100 mA is a relatively small figure when compared to the current that may flow in an earth fault without such protection (hundred of amps)
- A 300/500 mA RCCB may be used where only fire protection is required. eg., on lighting circuits, where the risk of electric shock is small
- RCDs are an extremely effective form of shock protection
Limitation of RCCB:
- Standard electromechanical RCCBs are designed to operate on normal supply waveforms and cannot be guaranteed to operate where none standard waveforms are generated by loads. The most common is the half wave rectified waveform sometimes called pulsating dc generated by speed control devices, semi conductors, computers and even dimmers.
- Specially modified RCCBs are available which will operate on normal ac and pulsating dc.
- RCDs don’t offer protection against current overloads: RCDs detect an imbalance in the live and neutral currents. A current overload, however large, cannot be detected. It is a frequent cause of problems with novices to replace an MCB in a fuse box with an RCD. This may be done in an attempt to increase shock protection. If a live-neutral fault occurs (a short circuit, or an overload), the RCD won’t trip, and may be damaged. In practice, the main MCB for the premises will probably trip, or the service fuse, so the situation is unlikely to lead to catastrophe; but it may be inconvenient.
- It is now possible to get an MCB and and RCD in a single unit, called an RCBO (see below). Replacing an MCB with an RCBO of the same rating is generally safe.
- Nuisance tripping of RCCB: Sudden changes in electrical load can cause a small, brief current flow to earth, especially in old appliances. RCDs are very sensitive and operate very quickly; they may well trip when the motor of an old freezer switches off. Some equipment is notoriously `leaky’, that is, generate a small, constant current flow to earth. Some types of computer equipment, and large television sets, are widely reported to cause problems.
- RCD will not protect against a socket outlet being wired with its live and neutral terminals the wrong way round.
- RCD will not protect against the overheating that results when conductors are not properly screwed into their terminals.
- RCD will not protect against live-neutral shocks, because the current in the live and neutral is balanced. So if you touch live and neutral conductors at the same time (e.g., both terminals of a light fitting), you may still get a nasty shock.
ELCB (Earth Leakage Circuit Breaker):
- Phase (line), Neutral and Earth wire connected through ELCB.
- ELCB is working based on Earth leakage current.
- Operating Time of ELCB:
- The safest limit of Current which Human Body can withstand is 30ma sec.
- Suppose Human Body Resistance is 500Ω and Voltage to ground is 230 Volt.
- The Body current will be 500/230=460mA.
- Hence ELCB must be operated in 30maSec/460mA = 0.65msec
RCBO (Residual Circuit Breaker with OverLoad):
- It is possible to get a combined MCB and RCCB in one device (Residual Current Breaker with Overload RCBO), the principals are the same, but more styles of disconnection are fitted into one package
Difference between ELCB and RCCB.
- ELCB is the old name and often refers to voltage operated devices that are no longer available and it is advised you replace them if you find one.
- RCCB or RCD is the new name that specifies current operated (hence the new name to distinguish from voltage operated).
- The new RCCB is best because it will detect any earth fault. The voltage type only detects earth faults that flow back through the main earth wire so this is why they stopped being used.
- The easy way to tell an old voltage operated trip is to look for the main earth wire connected through it.
- RCCB will only have the line and neutral connections.
- ELCB is working based on Earth leakage current. But RCCB is not having sensing or connectivity of Earth, because fundamentally Phase current is equal to the neutral current in single phase. That’s why RCCB can trip when the both currents are deferent and it withstand up to both the currents are same. Both the neutral and phase currents are different that means current is flowing through the Earth.
- Finally both are working for same, but the thing is connectivity is difference.
- RCD does not necessarily require an earth connection itself (it monitors only the live and neutral).In addition it detects current flows to earth even in equipment without an earth of its own.
- This means that an RCD will continue to give shock protection in equipment that has a faulty earth. It is these properties that have made the RCD more popular than its rivals. For example, earth-leakage circuit breakers (ELCBs) were widely used about ten years ago. These devices measured the voltage on the earth conductor; if this voltage was not zero this indicated a current leakage to earth. The problem is that ELCBs need a sound earth connection, as does the equipment it protects. As a result, the use of ELCBs is no longer recommended.
MCB Selection:
- The first characteristic is the overload which is intended to prevent the accidental overloading of the cable in a no fault situation. The speed of the MCB tripping will vary with the degree of the overload. This is usually achieved by the use of a thermal device in the MCB.
- The second characteristic is the magnetic fault protection, which is intended to operate when the fault reaches a predetermined level and to trip the MCB within one tenth of a second. The level of this magnetic trip gives the MCB its type characteristic as follows: – ·
- Type Tripping Current Operating Time
- Type B 3 To 5 time full load current 0.04 To 13 Sec
- Type C 5 To 10 times full load current 0.04 To 5 Sec
- Type D 10 To 20 times full load current 0.04 To 3 Sec
- The third characteristic is the short circuit protection, which is intended to protect against heavy faults maybe in thousands of amps caused by short circuit faults.
- The capability of the MCB to operate under these conditions gives its short circuit rating in Kilo amps (KA). In general for consumer units a 6KA fault level is adequate whereas for industrial boards 10KA fault capabilities or above may be required.
Fuse and MCB characteristics
- Fuses and MCBs are rated in amps. The amp rating given on the fuse or MCB body is the amount of current it will pass continuously. This is normally called the rated current or nominal current.
- Many people think that if the current exceeds the nominal current, the device will trip, instantly. So if the rating is 30 amps, a current of 30.00001 amps will trip it, right? This is not true.
- The fuse and the MCB, even though their nominal currents are similar, have very different properties.
- For example, For 32Amp MCB and 30 Amp Fuse, to be sure of tripping in 0.1 seconds, the MCB requires a current of 128 amps, while the fuse requires 300 amps.
- The fuse clearly requires more current to blow it in that time, but notice how much bigger both these currents are than the `30 amps’ marked current rating.
- There is a small likelihood that in the course of, say, a month, a 30-amp fuse will trip when carrying 30 amps. If the fuse has had a couple of overloads before (which may not even have been noticed) this is much more likely. This explains why fuses can sometimes `blow’ for no obvious reason
- If the fuse is marked `30 amps’, but it will actually stand 40 amps for over an hour, how can we justify calling it a `30 amp’ fuse? The answer is that the overload characteristics of fuses are designed to match the properties of modern cables. For example, a modern PVC-insulated cable will stand a 50% overload for an hour, so it seems reasonable that the fuse should as well.
Typical methods of provision of the main earthing terminal:
Supply type code : TN-S
- Supplier provides a separate earth connection, usually direct from the distribution station and via the metal sheath of the supply cable.
Supply type code : TN-C-S
- Supplier provides a combined earth/neutral connection; your main earth terminal is connected to their neutral
Supply type code : TT
- Supplier provides no earth; you have an earth spike near your premises.




All the details super, excelant. But i need one clearance. Fuse is fast of action compare to MCB.its true also, but u mention here fuse need more current to trip the circuit compare to MCB
Thanks You Sir, For ur help/information.
i m Mr.sonam Wangdi, Engineer (Electrical ) in Bhutan(Known as land of thunder dragon) ,Asia.
here , i would like to know about more in power system i.e power distribution system…
thank you.
Thanks for all above notes.
Sir i need the formula or procedure of how to selection of a mcb/mccb in any load.
Thanking you
Regards
Dev
The topics on your site are very much interesting & important for us. It give a big help and give additional technical knowledge that we can used in our job.
Sir can you publish also about Power Distribution system & Protection system in both transmission & distribution? Thanks and more power.
Thank u very mch Sir !!!!!!!!
Dear jignesh sir,
i am having doubt on this which one is correct tell me, Fuses or circuit breaker which is fast breaking the circuit.
comparison between fuse and circuit breaker
Fuses provide excellent motor protection at a relatively low cost. During a fault condition, fuses protect the branch circuit faster than circuit breakers. A fuse element can melt faster than a circuit breaker can open its contacts. Also, the fuse rating is typically less than the circuit breaker rating for a given motor, based on the NEC®.
Another advantage of fuses is their high interrupting rating. During a short circuit, extremely high currents can pass through the branch circuit while the protection device is opening. This can weld the contacts on a circuit breaker, preventing it from opening properly. Class CC fuses have an interrupting rating of 200,000 amps symmetrical. Class J fuses are available with an interrupting rating of 300,000 amps symmetrical. By using fuse protection, equipment can be connected directly to the main power feed in a building.
Despite their higher cost and slower response time, circuit breakers have advantages as well. Circuit breakers are much easier to troubleshoot than fuses. When external handles are installed, it is obvious when a circuit breaker has tripped. The circuit may then be locked out for motor maintenance. Upon completion, there is no need to procure the proper fuses or install them. During this down time, other circuits may remain on without any risk of shock to personnel.
Regards
Santhosh
Is it possible to check earth connection integrity when ELCB is connected on incomer side?
Dear Sir,
First of all thanx,
I have one question that which is better for house hold ?
Hai i wand electrical work safety
hi,
I want to ask some basic thing that do we consider fault current for LV cable sizing ?
Fault current on LV bus remains approx. 50 kA for 1 sec., so if we are using outgoing MCB/MCCB and the fault current remains in the circuit for 100 ms.
then fault current will apprx. 16 kA so we have to go for min. 185 sq. mm. cable.
But we even use 2.5/4/6 sq.mm. cable in LT circuit for lesser load demand.
MCB is available for 10 kA so it is also difficult to use MCB’s in this circuit, even MCB can’t be use in LDB’s for substation lighting as the fault current will not drop to 10 kA up to these LDB’s.
Dear Sir,
Greetings!
Thank you for the informative article… Some of the equipment terms are relatively new to me, though am aware of the MCB… I have a couple of queries if you could kindly help me out with them that would be of great help…
1. Where can I find these devices – ELCB and RCBO since some of the electric device dealers and electricians included were unaware of the same other than MCBs – Am from Bangalore any info of the Brand and dealer would be much appreciated…
2. I have 3 Large MCBs installed at the Meters location for each of the Lines (3Phase) and indoors smaller MCBs that control the internal layout in terms of sections…. I had a 6ft Pit dug out and installed a GI Pipe with Copper plate at the bottom and screw and the required Copper wire and had them filled with Salt and Charcoal…. yet some time back had the MCB at borewell starter burn out without any of the MCBs tripping we identified the burnout by smell… the electrician did change the MCB to a smaller capacity and the problem was resolved… a few days back we had an issue with the TV and again the Technician blamed the fluctuation as the culprit…. another incident was while installing lights during diwali… we did get an electric shock,but the MCBs remained in their on Position… My question is we have installed quite a few MCBs Brand Legrand hoping they would adequately keep the residents and equipment protected… but they seem inadequate, these were installed as per the Electricians & Engineers specification in terms of electric ratings… Would you suggest we install the ELCB and the RCBO to achieve a complete cover if yes do they need to be installed at the meters end where the inputs are or internally where the Circuit Breakers are installed (Must add internally at the MCBs location there arent any free slots to accommodate)
3. I remember while vacationing at one of the hotels each time there was a powerful lightning strike the power used to trip and be back on and yet none of the bulbs would blow out… used to wonder what kind of equipment was installed…. Just a thought sharing…
Any help in this regard would be highly appreciated…
Regards
Anish
Jignesh parmarji,
We are constructing housing quarters . The conducting is of concealed type. ALl our power ,Telephone wiring ,Inetnet wiring & Cable TV Wiring goes on the roof and comes down through the walls and ends at specified heights. Now our client wants that the Telephone,TV,Internet wiring to be below the floor (Below the tiles.).In this matter I want to know wheather it is permissible according to IndianTelegraphic Rules.Kindly guide me. If you give me your mobile number it will be more helpful.
good
sir..1 qstion..wht hppen to the electricity in final circuit when one mcb trip..explain
i need ELCB&RCCB circut diagram
Thank u sir 4 helping me out
i have one question elcb some time triping (mean after 10 day or 2o day why
your all updates are very useful to me
can you explain how to select switch gear on H.T side with step by step, and what are the factors need
Thanks in advance for all repliers
my mail id is h_rahman21@yahoo.com
realy ur doing great job
Regards,
Rahman
SIR YOUR ARTICLE VERY USEFUL FOR ME.I HAVE ONE QUSTION THAT I HAVE ONLY ONE RCCB AND ONE DP MCB .CAN I MAKE RCBO USIN THESE ITEMS
Similar to tripping characteristics of MCB(tyes B,C,D etc) please give same for MCCB for various types of OC/SC/EF protection ranges. Also give for other types of MCBs. Give tripping curves of MCBs and MCCBs.
Thanks for your blog explaining the circuit breakers. It helps non technical people like me.
Thanks for your blog explaining the circuit breakers. It helps non electrical trade people also
we r working of project on kirloskar diesel generating set.
the problem is that the dg set works at lower efficiency.
we need the solution of this problem.
it must be electrical view solution not mechanical.
we also need some written material on it.please elp us.
f:-hardik khalas
hardikkhalas@yahoo.com